The Lithonia Lighting Quantum ELM2L M12 is a contemporary LED emergency light designed to provide reliable illumination during power outages. This unit features two adjustable LED lamp heads, delivering a combined 220 lumens for effective light distribution in various commercial and industrial settings.

મુખ્ય લાક્ષણિકતાઓમાં શામેલ છે:

  • 90 Minutes of Illumination: Provides emergency lighting for 90 minutes upon power loss.
  • Aimable LED Lamp વડાઓ: Two 1.2W white LED lamp heads with a 10-year typical lifespan, offering 220 total lumens.
  • ટકાઉ બાંધકામ: Flame-rated 5VA thermoplastic housing, impact-resistant white casing.
  • Integrated Test Switch: Features an integrated test switch and bi-color LED status indicator for easy system checks.
  • Maintenance-Free Battery: Rechargeable nickel-cadmium battery requires no maintenance.
  • સરળ સ્થાપન: Designed for surface mounting on walls or ceilings, fitting standard junction boxes.
  • ડ્યુઅલ વોલ્યુમtage: Compatible with 120/277V electrical systems.
  • અનુપાલન: UL listed, meets UL 924, NFPA 101, NEC, Title 20, and OSHA standards.
Lithonia Lighting Quantum ELM2L M12 Emergency Light, front view
આકૃતિ 1: ફ્રન્ટ view of the Lithonia Lighting Quantum ELM2L M12 Emergency Light.

2. સલામતી માહિતી

Read all instructions carefully before installation and operation. Failure to follow these instructions may result in electric shock, fire, or other hazards, which could cause property damage, personal injury, or death.

  • ઇલેક્ટ્રિકલ સલામતી: All wiring should be performed by a qualified electrician in accordance with national and local electrical codes. Ensure power is disconnected at the circuit breaker before installation or servicing.
  • ઉત્પાદનનો ઉપયોગ: This product is intended for indoor damp locations (50°F to 104°F / 10°C to 40°C). Do not use in hazardous locations or with dimmers.
  • બેટરી સલામતી: The unit contains a nickel-cadmium battery. Dispose of batteries properly according to local regulations.
  • દરખાસ્ત 65 ચેતવણી: આ ઉત્પાદનમાં કેલિફોર્નિયા રાજ્યને કેન્સર અને જન્મજાત ખામી અથવા અન્ય પ્રજનન નુકસાન પહોંચાડવા માટે જાણીતા રસાયણો હોઈ શકે છે.

3. પેકેજ સામગ્રી

પેકેજ ખોલતી વખતે ખાતરી કરો કે બધા ઘટકો હાજર છે અને તેમને કોઈ નુકસાન થયું નથી:

  • Lithonia Lighting Quantum ELM2L M12 Emergency Light Fixture
  • માઉન્ટિંગ હાર્ડવેર (સ્ક્રૂ, વાયર નટ્સ)
  • સૂચના માર્ગદર્શિકા

4. સ્થાપન

The ELM2L M12 is designed for easy surface mounting on walls or ceilings. The back plate is compatible with most standard junction boxes.

4.1 માઉન્ટ કરવાનું પગલું

  1. પાવર ડિસ્કનેક્ટ કરો: Turn off power at the circuit breaker before beginning installation.
  2. Remove Back Assembly: Carefully remove the back assembly from the main body of the fixture.
  3. વાયરિંગ કનેક્ટ કરો: Hold the back plate up to the junction box. Use wire nuts to connect the fixture wires to the junction wires: green to green (ground), black to black, and white to white.
  4. સુરક્ષિત બેક પ્લેટ: Push excess wires into the junction box. Align the keyholes on the back of the fixture housing with the junction box screw holes. Lift the fixture up, install screws, and tighten them to secure the housing assembly to the wall or ceiling.
  5. બેટરી કનેક્ટ કરો: Within the main housing, connect the battery plug to the charger board. Ensure the battery cable is routed to avoid interference with the AC input connector or other components. The plug-and-play design allows for easy replacement of components.
  6. Re-install Main Body: Re-install the main body of the fixture onto the secured back plate.
  7. પાવર પુન Restસ્થાપિત કરો: Turn on electricity at the circuit breaker.
અન્ડરસાઇડ view of the emergency light showing the mounting plate and wiring access.
આકૃતિ 2: અન્ડરસાઇડ view of the ELM2L M12, illustrating the mounting plate and wiring access points.
Diagram showing the dimensions of the Lithonia Lighting Quantum ELM2L M12 Emergency Light.
Figure 3: Product dimensions: 9.72" L x 3.10" W x 4.68" H.

૧.૭ ઇન્સ્ટોલેશન વિડિઓ

Video 1: This video provides a visual guide for installing the ELM2L Emergency Lighting fixture, demonstrating the steps from unboxing to final mounting and wiring connections.

5. ઓપરેટિંગ સૂચનાઓ

Once installed and power is restored, the emergency light will begin charging its internal battery. The bi-color LED status indicator will show the charging status.

5.1 Manual Testing

The unit is equipped with a manual test switch. Press and hold the test button to initiate a manual test. The LED lamp heads should illuminate, indicating that the battery backup system is functional. Release the button to return to normal operation.

Regular testing is crucial to ensure the unit operates correctly during an emergency. Refer to local codes for recommended testing frequency (e.g., monthly 30-second tests, annual 90-minute discharge tests).

6. જાળવણી

The ELM2L M12 emergency light is designed for minimal maintenance. The nickel-cadmium battery is maintenance-free.

  • સફાઈ: Periodically clean the exterior of the fixture with a soft, dry cloth. Do not use abrasive cleaners or solvents.
  • બેટરી રિપ્લેસમેન્ટ: While designed for a long lifespan, batteries may eventually require replacement. The plug-and-play design facilitates easy battery replacement by a qualified technician.
  • Lamp હેડ એડજસ્ટમેન્ટ: The two LED lamp heads are aimable. Adjust them as needed to direct light to the required egress path.

7. મુશ્કેલીનિવારણ

If the emergency light is not functioning as expected, refer to the following common issues and solutions:

સમસ્યાસંભવિત કારણઉકેલ
Unit does not illuminate during power outage or test.No AC power; Battery not connected or faulty; Battery not charged.Check circuit breaker. Ensure battery is properly connected. Allow 24 hours for initial charge. Replace battery if necessary.
LED indicator is off or red.No AC power; Battery fault; Charger fault.Check AC power. Perform battery test. If issue persists, contact customer support.
Emergency lights dim quickly.Battery not fully charged; Battery nearing end of life.Ensure unit is connected to continuous AC power. Replace battery if it fails to hold a charge.

8. સ્પષ્ટીકરણો

લક્ષણવિગત
મોડલ નંબરELM2L M12
બ્રાન્ડલિથોનિયા લાઇટિંગ
પરિમાણો (L x W x H)૧૨.૨" x ૧૪" x ૫૭.૨"
વજન1.31 lbs
રંગસફેદ
સામગ્રીથર્મોપ્લાસ્ટિક
પ્રકાશ સ્ત્રોતLED (2 aimable lamp heads)
તેજ220 Lumens (total)
વાટtage2.4 વોટ
ભાગtage120/277V Dual Voltage
બેટરીનો પ્રકારNickel-Cadmium (maintenance-free)
ઈમરજન્સી ઓપરેશન90 મિનિટ
માઉન્ટિંગ પ્રકારસીલિંગ માઉન્ટ, વોલ માઉન્ટ
ઓપરેટિંગ તાપમાન50°F થી 104°F (10°C થી 40°C)
પ્રમાણપત્રોUL Listed, UL 924, NFPA 101, NEC, Title 20, OSHA

9. વોરંટી અને સપોર્ટ

The Lithonia Lighting Quantum ELM2L M12 Emergency Light comes with a ૧ વર્ષની મર્યાદિત ઉત્પાદકની વોરંટી. For warranty claims or technical support, please visit the official Lithonia Lighting webસાઇટ અથવા તેમની ગ્રાહક સેવાનો સંપર્ક કરો.

For more detailed product information and support resources, visit: lithonia.acuitybrands.com

9.1 ઉત્પાદન ઓવરview વિડિયો

વિડિઓ ૧: આ વિડિઓ એક સામાન્ય ઓવર પ્રદાન કરે છેview of emergency lighting products, including features and benefits relevant to the ELM2L M12.

9.2 Quantum vs. Basics Comparison Video

Video 3: This video compares the Quantum series, including the ELM2L M12, with Lithonia Lighting Basics products, highlighting differences in coverage and application suitability.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.