Shinko ACS2 Digital Indicating Controller

ઉત્પાદન માહિતી
- Product Name: Mikroprocesorowy regulator temperatury PID z serii ACS2
- મોડેલ: ACS2
- ઉત્પાદક: https://acse.pl
- Type: Digital Indicating Controller
ઉત્પાદન વપરાશ સૂચનાઓ
Before using the product, please read and follow the safety precautions provided in the manual. The safety precautions include warnings and cautions to prevent accidents and ensure safe operation.
- ઇન્સ્ટોલેશન સાવચેતીઓ:
- During installation, ensure that the instrument is placed on a stable surface and away from flammable materials due to the flame-resistant resin construction.
- વાયરિંગ સાવચેતીઓ:
- Follow the wiring instructions carefully to avoid any electricalhazards. Make sure to use appropriate wiring materials and connections.
- Operation and Maintenance Precautions:
- Operate the controller according to the provided instructions. Regular maintenance is important to ensure proper functioning and longevity of the product.
- સલામતી ધોરણોનું પાલન:
- Adhere to safety standards to prevent any risks associated withthe product. Non-compliance may lead to malfunction or damage to the product.
સામગ્રી:
- મોડલ
- મોડલ
- મોડેલ લેબલ કેવી રીતે વાંચવું
- Names and Functions of Controller
- કંટ્રોલ પેનલ પર માઉન્ટ કરવાનું
FAQ
પ્ર: જો નિયંત્રક ભૂલ કોડ દર્શાવે તો મારે શું કરવું જોઈએ?
A: Refer to the troubleshooting section in the manual to identify the error code and follow the recommended solutions.
Q: Can I use this controller for industrial applications?
A: Yes, this controller can be used for industrial applications, but ensure compliance with safety regulations and standards.
Mikroprocesorowy regulator temperatury PID z serii ACS2 – https://acse.pl
DIGITAL INDICATING CONTROLLER
ACS2
સૂચના માર્ગદર્શિકા
પ્રસ્તાવના
ખરીદી બદલ આભારasing our digital indicating controller ACS2. This manual contains instructions for the mounting, functions, operations and notes when operating the BCx2. To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.
આ માર્ગદર્શિકામાં વપરાયેલ સંક્ષેપો
સંક્ષેપ
મુદત
PV
પ્રક્રિયા ચલ
SV
ઇચ્છિત મૂલ્ય
MV
મેનિપ્યુલેટેડ ચલ
DV
વિચલન
આઉટ 1
નિયંત્રણ આઉટપુટ OUT1
આઉટ 2
નિયંત્રણ આઉટપુટ OUT2
AT
ઓટો-ટ્યુનિંગ
આ માર્ગદર્શિકામાં વપરાયેલ અક્ષરો
સંકેત
Number, / -1 0 1 2 3 4 5 6 7 8 9
સંકેત
આલ્ફાબેટ
ABCDE FGH IJK LM
સંકેત
આલ્ફાબેટ
NOPQR STU VWX YZ
નોંધો
· આ સાધનનો ઉપયોગ માર્ગદર્શિકામાં વર્ણવેલ સ્પષ્ટીકરણો અનુસાર થવો જોઈએ. જો તેનો ઉપયોગ સ્પષ્ટીકરણો અનુસાર કરવામાં આવતો નથી, તો તે ખરાબ થઈ શકે છે અથવા આગનું કારણ બની શકે છે.
· ચેતવણીઓ, સાવચેતીઓ અને સૂચનાઓનું પાલન કરવાની ખાતરી કરો. જો તેઓ અવલોકન ન કરવામાં આવે તો, ગંભીર ઇજા અથવા ખામી સર્જાઈ શકે છે.
· આ સૂચના માર્ગદર્શિકાની સામગ્રી સૂચના વિના બદલવાને પાત્ર છે. · આ સૂચના માર્ગદર્શિકાની સામગ્રી સાચી છે તેની ખાતરી કરવા માટે કાળજી લેવામાં આવી છે, પરંતુ જો ત્યાં કોઈ હોય તો
doubts, mistakes or questions, please inform our sales department. · This instrument is designed to be installed through a control panel indoors. If it is not, measures must be
taken to ensure that the operator cannot touch power terminals or other high voltage વિભાગો. · આ દસ્તાવેજનું કોઈપણ અનધિકૃત ટ્રાન્સફર અથવા નકલ, આંશિક અથવા સંપૂર્ણ રીતે, પ્રતિબંધિત છે. · શિન્કો ટેક્નોસ કંપની લિમિટેડ, ઉપયોગના પરિણામે થયેલા કોઈપણ નુકસાન અથવા ગૌણ નુકસાન(ઓ) માટે જવાબદાર નથી.
આ ઉત્પાદન, કોઈપણ પરોક્ષ નુકસાન સહિત.
સલામતી સાવચેતીઓ (અમારા ઉત્પાદનોનો ઉપયોગ કરતા પહેલા આ સાવચેતીઓ વાંચવાની ખાતરી કરો.)
સલામતીની સાવચેતીઓને શ્રેણીઓમાં વર્ગીકૃત કરવામાં આવી છે: “ચેતવણી” અને “સાવધાન”. સંજોગો પર આધાર રાખીને, સાવચેતી દ્વારા સૂચવવામાં આવેલી કાર્યવાહી ગંભીર પરિણામોમાં પરિણમી શકે છે, તેથી ઉપયોગ માટેના નિર્દેશોનું પાલન કરવાની ખાતરી કરો.
ચેતવણી પ્રક્રિયાઓ જે ખતરનાક પરિસ્થિતિઓમાં પરિણમી શકે છે અને મૃત્યુ અથવા ગંભીર ઈજાનું કારણ બની શકે છે, જો યોગ્ય રીતે હાથ ધરવામાં ન આવે તો.
Procedures which may lead to dangerous conditions and cause superficial to
Caution medium injury or physical damage or may degrade or damage the product, if not carried out properly.
– 2 –
ચેતવણી
· વિદ્યુત આંચકો અથવા આગને રોકવા માટે, ફક્ત શિન્કો અથવા લાયક સેવા કર્મચારીઓ આંતરિક એસેમ્બલીનું સંચાલન કરી શકે છે.
· વિદ્યુત આંચકો, આગ અથવા સાધનને થતા નુકસાનને રોકવા માટે, ભાગો બદલવાની કામગીરી ફક્ત શિન્કો અથવા લાયક સેવા કર્મચારીઓ દ્વારા જ હાથ ધરવામાં આવી શકે છે.
સલામતી સાવચેતીઓ
· સલામત અને સાચો ઉપયોગ સુનિશ્ચિત કરવા માટે, આ સાધનનો ઉપયોગ કરતા પહેલા આ માર્ગદર્શિકાને સારી રીતે વાંચો અને સમજો.
· આ સાધનનો ઉપયોગ ઔદ્યોગિક મશીનરી, મશીન ટૂલ્સ અને માપવાના સાધનો માટે કરવાનો છે. અમારી એજન્સી અથવા મુખ્ય કાર્યાલય સાથે હેતુ-ઉપયોગના પરામર્શ પછી સાચો ઉપયોગ ચકાસો. (જેમાં માનવ જીવન સંકળાયેલું છે તે તબીબી હેતુઓ માટે આ સાધનનો ક્યારેય ઉપયોગ કરશો નહીં.)
· External protection devices such as protective equipment against excessive temperature rise, etc. must be installed, as malfunction of this product could result in serious damage to the system or injury to personnel. Proper periodic maintenance is also required.
· આ સાધનનો ઉપયોગ આ માર્ગદર્શિકામાં વર્ણવેલ પરિસ્થિતિઓ અને વાતાવરણ હેઠળ થવો જોઈએ. શિન્કો ટેક્નોસ કંપની લિમિટેડ, આ માર્ગદર્શિકામાં અન્યથા જણાવેલ ન હોય તેવી પરિસ્થિતિઓ હેઠળ સાધનના ઉપયોગને કારણે થતી કોઈપણ ઈજા, જાનહાનિ અથવા નુકસાન માટે જવાબદારી સ્વીકારતી નથી.
મોડલ લેબલ પર ચેતવણી
સાવધાન
આ સાધનને યોગ્ય રીતે હેન્ડલ કરવામાં નિષ્ફળતાના પરિણામે આગ, ખામી, ખામી અથવા ઇલેક્ટ્રિક આંચકાને કારણે નાની અથવા મધ્યમ ઈજા અથવા મિલકતને નુકસાન થઈ શકે છે. તમે ઉત્પાદનને સંપૂર્ણપણે સમજો છો તેની ખાતરી કરવા માટે કૃપા કરીને ઉત્પાદનનો ઉપયોગ કરતા પહેલા આ માર્ગદર્શિકા વાંચો.
નિકાસ વેપાર નિયંત્રણ વટહુકમના સંદર્ભમાં સાવધાની
સામૂહિક વિનાશના શસ્ત્રો (એટલે કે લશ્કરી એપ્લિકેશનો, લશ્કરી સાધનો, વગેરે) માં ઘટક તરીકે ઉપયોગમાં લેવાતા અથવા ઉપયોગમાં લેવાતા આ સાધનને ટાળવા માટે, કૃપા કરીને અંતિમ વપરાશકર્તાઓ અને આ સાધનના અંતિમ ઉપયોગની તપાસ કરો. પુનર્વેચાણના કિસ્સામાં, ખાતરી કરો કે આ સાધન ગેરકાયદેસર રીતે નિકાસ કરવામાં આવ્યું નથી.
ઉપયોગ માટે સાવચેતીઓ
1. સ્થાપન સાવચેતી
સાવધાન
આ સાધનનો ઉપયોગ નીચેની પર્યાવરણીય પરિસ્થિતિઓ (IEC61010-1) હેઠળ કરવાનો છે: ઓવરવોલtage category , Pollution degree 2 Ensure the mounting location corresponds to the following conditions: · A minimum of dust, and an absence of corrosive gases · No flammable, explosive gases · No mechanical vibrations or shocks · No exposure to direct sunlight, an ambient temperature of -10 to 55 (14 to 131 ) that does not
change rapidly, and no icing · An ambient non-condensing humidity of 35 to 85 %RH · No large capacity electromagnetic switches or cables through which large current is flowing · No water, oil or chemicals or where the vapors of these substances can come into direct contact with
એકમ · મહેરબાની કરીને નોંધ કરો કે આ એકમનું આસપાસનું તાપમાન નિયંત્રણનું આસપાસનું તાપમાન નથી
panel must not exceed 55 (131 ) if mounted through the face of a control panel, otherwise the life of electronic components (especially electrolytic capacitors) may be shortened. Note · Avoid setting this instrument directly on or near flammable material even though the case
આ સાધન જ્યોત-પ્રતિરોધક રેઝિનથી બનેલું છે.
– 3 –
2. વાયરિંગ સાવચેતીઓ
સાવધાન
· સાધનમાં વાયરના અવશેષો ન છોડો, કારણ કે તે આગ અથવા ખરાબીનું કારણ બની શકે છે. · ઇન્સ્યુલેશન સ્લીવ સાથે સોલ્ડરલેસ ટર્મિનલનો ઉપયોગ કરો જેમાં વાયરિંગ કરતી વખતે M3 સ્ક્રૂ બંધબેસે છે.
instrument. · The terminal block of this instrument is designed to be wired from the left side. The lead wire must be
inserted from the left side of the terminal, and fastened with the terminal screw. · Tighten the terminal screw using the specified torque. If excessive force is applied to the screw when
tightening, the terminal screw or case may be damaged. · Do not pull or bend the lead wire on the terminal side when wiring or after wiring, as it could cause
malfunction. · When using a terminal cover for the BCS2, pass terminal wires numbered 7 to 12 into the holes of the
terminal cover. · This instrument does not have a built-in power switch, circuit breaker and fuse.
It is necessary to install a power switch, circuit breaker and fuse near the controller. (Recommended fuse: Time-lag fuse, rated voltage 250 V AC, rated current 2 A) · For a 24 V AC/DC power source, do not confuse polarity when using direct current (DC). · Do not apply a commercial power source to the sensor which is connected to the input terminal nor allow the power source to come into contact with the sensor. · Use a thermocouple and compensating lead wire according to the sensor input specifications of this controller. · Use the 3-wire RTD according to the sensor input specifications of this controller. · For DC voltage input, (+) side input terminal number of 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC differs from that of 0 to 1 V DC. For the input terminal number, the (+) side for 0 to 5 V DC, 1 to 5 V DC, and 0 to 10 V DC is 9 , and the (+) side for 0 to 1 V DC is 10 . · When using a relay contact output type, externally use a relay according to the capacity of the load to protect the built-in relay contact. · When wiring, keep input wires (thermocouple, RTD, etc.) away from controller AC power sources or load wires.
3. ઓપરેશન અને જાળવણી સાવચેતીઓ
સાવધાન
· It is recommended that AT be performed on the trial run. · Do not touch live terminals. This may cause electrical shock or problems in operation. · Turn the power supply to the instrument OFF when retightening the terminal or cleaning. Working on or touching the terminal with the power switched ON may result in severe injury or death
due to electrical shock. · Use a soft, dry cloth when cleaning the instrument. (Alcohol based substances may tarnish or deface the unit.) · As the display section is vulnerable, be careful not to put pressure on, scratch or strike it with a hard
પદાર્થ
4. Compliance with Safety Standards
સાવધાન
· Always install the recommended fuse described in this manual externally. · If the instrument is used in a manner not specified by the manufacturer, the protection provided by
the instrument may be impaired. · Use a device with reinforced insulation or double insulation for the external circuit connected to this
ઉત્પાદન
– 4 –
સામગ્રી
1. Model……………………………………………………………………………………………………………………………………… 8 1.1 Model ………………………………………………………………………………………………………………………………….. 8 1.2 How to Read the Model Label ………………………………………………………………………………………………… 9
2. Names and Functions of Controller ………………………………………………………………………………………….. 10 3. Mounting to the Control Panel …………………………………………………………………………………………………. 12
3.1 External Dimensions (Scale: mm) …………………………………………………………………………………………. 12 3.2 Panel Cutout (Scale: mm) ……………………………………………………………………………………………………. 12 3.3 CT External Dimensions (Scale: mm)……………………………………………………………………………………. 12 3.4 Mounting to, and Removal from, the Control Panel …………………………………………………………………. 13
3.4.1 How to Mount the Unit ………………………………………………………………………………………………….. 13 3.4.2 How to Remove the Mounting Frame and Unit ………………………………………………………………… 14 4. Wiring …………………………………………………………………………………………………………………………………… 15 4.1 Terminal Arrangement …………………………………………………………………………………………………………. 16 4.2 Lead Wire Solderless Terminal……………………………………………………………………………………………… 16 4.3 Terminal Cover …………………………………………………………………………………………………………………… 17 4.4 Wiring………………………………………………………………………………………………………………………………… 17 4.4.1 Power Supply ………………………………………………………………………………………………………………. 17 4.4.2 Control Output OUT1, OUT2 …………………………………………………………………………………………. 18 4.4.3 Input …………………………………………………………………………………………………………………………… 19 4.4.4 Event Output 1, Event Output 2, Event Output 3………………………………………………………………. 19 4.4.5 Insulated Power Output ………………………………………………………………………………………………… 19 4.4.6 CT Input………………………………………………………………………………………………………………………. 20 4.4.7 Serial Communication …………………………………………………………………………………………………… 21 4.4.8 Event Input ………………………………………………………………………………………………………………….. 23 4.4.9 External Setting Input……………………………………………………………………………………………………. 23 4.4.10 Transmission Output …………………………………………………………………………………………………….. 23 5. Outline of Key Operation and Each Mode …………………………………………………………………………………. 24 5.1 key Operation …………………………………………………………………………………………………………………….. 24 5.2 Modes ……………………………………………………………………………………………………………………………….. 26 5.3 Basic Operation after Power-ON…………………………………………………………………………………………… 28 6. Initial Setting………………………………………………………………………………………………………………………….. 34 6.1 Power-ON ………………………………………………………………………………………………………………………….. 38 6.2 Basic Operation of Settings………………………………………………………………………………………………….. 38 6.3 Initial Setting ………………………………………………………………………………………………………………………. 39 6.3.1 Input Setting Group ………………………………………………………………………………………………………. 39 6.3.2 EVT Input Setting Group ……………………………………………………………………………………………….. 43 6.3.3 EVT Output Setting Group …………………………………………………………………………………………….. 46 6.3.4 Transmission Output Setting Group………………………………………………………………………………… 53 6.3.5 External Setting Input Setting Group ………………………………………………………………………………. 54 6.3.6 Main Setting Group ………………………………………………………………………………………………………. 55 7. Settings ………………………………………………………………………………………………………………………………… 57 7.1 Main Setting Group……………………………………………………………………………………………………………… 57 7.2 Program Settings Group………………………………………………………………………………………………………. 59
– 5 –
7.3 AT Settings Group ………………………………………………………………………………………………………………. 62 7.4 PID Settings Group……………………………………………………………………………………………………………… 64 7.5 Alarm Setting Group ……………………………………………………………………………………………………………. 68 7.6 Input Setting Group …………………………………………………………………………………………………………….. 71 7.7 Output Setting Group ………………………………………………………………………………………………………….. 76 7.8 EVT Input Setting Group ……………………………………………………………………………………………………… 80 7.9 EVT Output Setting Group …………………………………………………………………………………………………… 83 7.10 Communication Setting Group ……………………………………………………………………………………………… 90 7.11 Transmission Output Setting Group ………………………………………………………………………………………. 92 7.12 External Setting Input Setting Group……………………………………………………………………………………… 93 7.13 Control Function Setting Group…………………………………………………………………………………………….. 94 7.14 Program Function Setting Group ………………………………………………………………………………………….. 96 7.15 Wait Setting Group ……………………………………………………………………………………………………………… 98 7.16 Other Setting Group ………………………………………………………………………………………………………….. 100 7.17 Maintenance Group …………………………………………………………………………………………………………… 105 8. Operation and Settings of Standard Functions…………………………………………………………………………. 107 8.1 Selecting an input type ………………………………………………………………………………………………………. 107 8.2 Selecting Fast-PID Control …………………………………………………………………………………………………. 108 8.3 Selecting Direct/Reverse Action ………………………………………………………………………………………….. 110 8.4 Performing Fixed Value Control ……………………………………………………………………………………………111 8.5 Setting PID Constants (by Performing AT)……………………………………………………………………………. 112 8.6 Performing Program Control ………………………………………………………………………………………………. 117 8.7 Event Output EV Allocation ………………………………………………………………………………………………. 129 8.8 Indicating MV, Remaining Time (Program Control)………………………………………………………………… 131 8.9 Items to be Initialized by Changing Settings …………………………………………………………………………. 132 9. Attached Function ………………………………………………………………………………………………………………… 134 9.1 Input Value Correction ……………………………………………………………………………………………………….. 134 9.2 Set Value Lock………………………………………………………………………………………………………………….. 136 9.3 Control Output OFF Function ……………………………………………………………………………………………… 137 9.4 Switching Auto/Manual Control (Auto/Manual Control Function)……………………………………………… 138 9.5 Data Clear and Program Clear……………………………………………………………………………………………. 140 10. Action Explanation ……………………………………………………………………………………………………………….. 141 10.1 OUT1 Action …………………………………………………………………………………………………………………….. 141 10.2 OUT1 ON/OFF Action ……………………………………………………………………………………………………….. 142 10.3 Heater Burnout Alarm Action ………………………………………………………………………………………………. 143 10.4 Alarm Action …………………………………………………………………………………………………………………….. 144 10.5 OUT2 (Heating/Cooling Control) Action……………………………………………………………………………….. 146 10.6 OUT2 (Heating/Cooling Control) Action (When Setting Dead Band) ……………………………………….. 146 10.7 OUT2 (Heating/Cooling Control) Action (When Setting Overlap Band) ……………………………………. 148 11. Specifications ………………………………………………………………………………………………………………………. 149 11.1 Standard Specifications……………………………………………………………………………………………………… 149 11.2 Optional Specifications ……………………………………………………………………………………………………….
– 6 –
12. Troubleshooting……………………………………………………………………………………………………………………. 168 12.1 Indication …………………………………………………………………………………………………………………………. 168 12.2 Key Operation…………………………………………………………………………………………………………………… 170 12.3 Control …………………………………………………………………………………………………………………………….. 171
13. Character Table ……………………………………………………………………………………………………………………. 172 13.1 Display Mode ……………………………………………………………………………………………………………………. 172 13.1.1 PV/SV Display Mode…………………………………………………………………………………………………… 172 13.1.2 MV Display Mode ……………………………………………………………………………………………………….. 172 13.1.3 Remaining Time Display Mode …………………………………………………………………………………….. 172 13.2 Settings……………………………………………………………………………………………………………………………. 173 13.2.1 Manual Control Mode………………………………………………………………………………………………….. 173 13.2.2 SV Setting (Direct Setting for Fix Value Control) …………………………………………………………….. 174 13.2.3 Setting Group …………………………………………………………………………………………………………….. 175
14. Key Operation Flowchart ………………………………………………………………………………………………………. 199
– 7 –
1. મોડલ
1.1 મોડલ
ACS2
–
Series name: ACS2 (W48×H48×D68 mm)
નિયંત્રણ આઉટપુટ
R(*5)
M(*1)
V 1 2 3 C
રિલે સંપર્ક: 1a બિન-સંપર્ક વોલ્યુમtage (for SSR drive) 12 V DC 15% Direct current: 4 to 20mA DC Direct current: 0 to 20mA DC DC voltage: 0 to 1V DC voltage: 0 to 5V DC voltage: 1 to 5V DC voltage: 0 to 10V Open collector
પાવર સપ્લાય વોલ્યુમtage Input Option
વિકલ્પ
0
100 to 240V AC, 24V DC, 48V DC
M
બહુ-શ્રેણી
0
કોઈ વિકલ્પો નથી
1
Event output EV2 (*1)
EV2
2
Event output EV3 (*2)
EV3
3
Heating/Cooling control O2(SSR/A) (*4) O2(SSR/A)
4
Insulated power output (*6)
P24
0 No options
1 Serial communication + Heater burnout C5W(20A)
alarm (20A)
2 Serial communication + Heater burnout C5W(100A)
alarm (100A)
3 Heater burnout alarm (20A) (*3)
W(20A)
4 Heater burnout alarm (100A) (*3)
W(100A)
5 Transmission output (4-20mA) (*3)
TA
6 Transmission output (0-1V) (*3)
TV
7 Transmission output (0-10V) (*3)
TV
8 External setting input (*3)
EA
9 Serial communication (*3)
C5
A Event input 4 points
EI
(*1): When OUT1 is selected in [Event 2 allocation selection], the output becomes multi-output and
SSR output, current output, and relay output can be selected.
(*2): Event output 3 points is common.
(*3): Options other than C5W and EI will simultaneously add Event input 2 points.
(*4): When O2 is selected, the output of cooling side can be selected SSR output and current output.
However, cooling output of relay output is not possible.
When cooling output is desired for relay output, it can be used by selecting OUT2 in [Event 2
allocation selection].
(*5): To use the heating side as a relay output in heating/cooling control, select R.
(*6): To use the insulated power output for relay output, select R.
– 8 –
મોડલ લેબલ

1.2 How to Read the Model Label The model label is attached to the right side of the case.
(e.g.) ACS2M0M-12
(ફિગ. 1.2-1- XNUMX-XNUMX)
ના.
વર્ણન
Example
ટર્મિનલ વ્યવસ્થા
ACS2M0M-12 (*1)
મોડલ
ACS2M0M-12
વિકલ્પ
C5W(100A) [Serial communication + Heater burnout
alarm (100 A)] (*2)
સીરીયલ નંબર
નંબર 253F05000
Control output,
O1: MULTI-OUTPUT (Control output OUT1)
ઇવેન્ટ આઉટપુટ
EV1: 3 A 250 V AC(Event output EV1)
EV2: 3 A 250 V AC(Event output EV2)
પાવર સપ્લાય વોલ્યુમtage,
DC 24V/48V 7W, 100 to 240 V AC 50/60Hz 15 VA
પાવર વપરાશ
(*1): Terminal arrangement diagram differs depending on the model.
(*2): For Heater burnout alarm output (C5W, EIW, W options), CT rated current is entered in
bracket ( ).
– 9 –
Names and Functions of Controller

(ફિગ. 2-1- XNUMX-XNUMX)
ડિસ્પ્લે નં.
Name PV display
એસ.વી. ડિસ્પ્લે
તાપમાન એકમ પ્રદર્શન
MEMO/STEP display
વર્ણન
Indicates PV. Indicates setting characters in each setting mode. Indicates SV. Indicates the set data in each setting mode. In monitor mode, indicates the MV or remaining time (program control). Displays the temperature unit. (Displayed only for thermocouple and RTD ranges) Indicates Set value memory number (Fixed value control) or Program step number.
– 10 –
ક્રિયા સૂચકાંકો
ના.
નામ
SV indicator
MV indicator
યાદી
સૂચક
STEP indicator
O1
O2
EV1 EV2 EV3 AT MAN R/L T/R
લોક
વર્ણન
Lit when SV display shows the set value. Lit when SV display shows the MV. Lit when set value memory function is enabled during fixed value control selection. Lit when program control is selected. Lit when control output is ON or when heating output (optional: EV2, O2 (SSR/A)) is ON. For direct current current or DC voltage outputs, flashes corresponding to the MV in 250 ms cycles. Lit when cooling output (optional: EV2, O2 (SSR/A)) is ON. For direct current current or DC voltage outputs, flashes corresponding to the MV in 250 ms cycles. Lit when Event output 1 is ON. Lit when Event output 2 (optional: EV2) is ON. Lit when Event output 3 (optional: EV3) is ON. Flashes while AT or `AT on startup’ is performing. Lit when manual control is performed. Lit when remote is selected for external setting input. Lit during Serial communication (C5W, C5 options) TX (transmitting) output. Lit when set value lock mode is enabled.
કી નં.
Name UP key
DOWN કી
PF key
OUT/OFF key MODE key
વર્ણન
Increases the numeric value. During program control, pressing for 1 second activates the advance function. Decreases the numeric value. During program control, pressing for 1 second activates the hold function. Operate the selected function in the PF key function selection. In setting mode, select the number of digits to be entered. Operate the selected function in the OUT/OFF key function selection. Switches a setting mode, and registers the set data. By pressing this key for 3 seconds during RUN mode, the unit enters
Monitor mode.
કન્સોલ કનેક્ટર
ના.
નામ
કન્સોલ
કનેક્ટર
વર્ણન
By connecting the tool cable (CMD-001, sold separately), the following operations can be conducted from an external computer using the Console software SWC-ACS201M. · Reading and setting of SV, PID and various set values · Reading of PV and action status · Function change
– 11 –
3. કંટ્રોલ પેનલ પર માઉન્ટ કરવાનું
3.1 External Dimensions (Scale: mm) Gasket
માઉન્ટ કરવાનું ફ્રેમ
ટર્મિનલ કવર (અલગથી વેચાય છે)
૯૮.૫ ૧૦૪.૫(*)
6 0
8.4 48
(*): When the terminal cover is used. (Fig. 3.1-1)
58.8 (*) 65.1(*)
3.2 પેનલ કટઆઉટ (સ્કેલ: mm)
સાવધાન
જો કંટ્રોલર માટે હોરીઝોન્ટલ ક્લોઝ માઉન્ટિંગનો ઉપયોગ કરવામાં આવે છે, તો IP66 સ્પષ્ટીકરણ (ડ્રિપ-પ્રૂફ/ડસ્ટ-પ્રૂફ) સાથે ચેડા થઈ શકે છે અને બધી વૉરંટી અમાન્ય થઈ જશે.
0.5 0
45
75
45
0.5 0
45
0.5 0
n×48-300.5
Horizontal close mounting, n: Number of units mounted (Fig. 3.2-1)
3.3 CT External Dimensions (Scale: mm) CTL-6-S-H(for 20A)
CTL-12-S36-10L1U(for 100A)
(Fig. 3.3-1) – 12 –
3.4 Mounting to, and Removal from, the Control Panel
ચેતવણી
As the mounting frame of the ACS2 is made of resin, do not use excessive force while tightening screws, or the mounting frame could be damaged. Tighten screws with one rotation upon the screw tips touching the panel. The torque is 0.05 to 0.06 N·m.
3.4.1 How to Mount the Unit Mount the controller vertically to the flat, rigid panel to ensure it adheres to the Drip-proof/Dust-proof specification (IP66). If the lateral close mounting is used for the controller, IP66 specification (Drip-proof/Dust-proof) may be compromised, and all warranties will be invalidated. Mountable panel thickness: 1 to 5 mm
(1) Insert the controller from the front side of the control panel. (Fig. 3.4.1-1) If the Drip-proof/Dust-proof specification (IP66) is not necessary, the gasket may be removed (Please keep in mind the warranty is void if gasket is removed).
(2) Insert the mounting frame until it comes into contact with the panel, and fasten with screws. Tighten screws with one rotation upon the screw tips touching the panel. (Fig. 3.4.1-2) The torque is 0.05 to 0.06 N·m.
ગાસ્કેટ
માઉન્ટ કરવાનું ફ્રેમ
(ફિગ. 3.4.1-1- XNUMX-XNUMX)
(ફિગ. 3.4.1-2- XNUMX-XNUMX)
– 13 –
3.4.2 How to Remove the Mounting Frame and Unit (1) Turn the power to the unit OFF, and disconnect all wires before removing the mounting frame. (2) Insert a flat blade screwdriver between the mounting frame and unit ( 1 ). (3) Slowly push the frame upward using the screwdriver ( 2 ), while pushing the unit toward the panel ( 3 ). (4) Repeat step (2) and slowly push the frame downward using the screwdriver for the other side. The frame can be removed little by little by repeating these steps.
(ફિગ. 3.4.2-1- XNUMX-XNUMX)
– 14 –
4. વાયરિંગ ચેતવણી
વાયરિંગ અથવા તપાસ કરતા પહેલા ઇન્સ્ટ્રુમેન્ટનો પાવર સપ્લાય બંધ કરો. પાવર ચાલુ કરીને ટર્મિનલ પર કામ કરવું અથવા તેને સ્પર્શ કરવાથી વિદ્યુત આંચકાને કારણે ગંભીર ઈજા અથવા મૃત્યુ થઈ શકે છે.
સાવધાન
· સાધનમાં વાયરના અવશેષો ન છોડો, કારણ કે તે આગ અથવા ખરાબીનું કારણ બની શકે છે. · ઇન્સ્યુલેશન સ્લીવ સાથે સોલ્ડરલેસ ટર્મિનલનો ઉપયોગ કરો જેમાં વાયરિંગ કરતી વખતે M3 સ્ક્રૂ બંધબેસે છે.
instrument. · The terminal block of this instrument is designed to be wired from the left side. The lead wire must be
inserted from the left side of the terminal, and fastened with the terminal screw. · Tighten the terminal screw using the specified torque. If excessive force is applied to the screw when
tightening, the terminal screw or case may be damaged. · Do not pull or bend the lead wire on the terminal side when wiring or after wiring, as it could cause
malfunction. · When using a terminal cover for the BCS2, pass terminal wires numbered 7 to 12 into the holes of the
terminal cover. · This instrument does not have a built-in power switch, circuit breaker and fuse.
It is necessary to install a power switch, circuit breaker and fuse near the controller. (Recommended fuse: Time-lag fuse, rated voltage 250 V AC, rated current 2 A) · For a 24 V AC/DC power source, do not confuse polarity when using direct current (DC). · Do not apply a commercial power source to the sensor which is connected to the input terminal nor allow the power source to come into contact with the sensor. · Use a thermocouple and compensating lead wire according to the sensor input specifications of this controller. · Use the 3-wire RTD according to the sensor input specifications of this controller. · For DC voltage input, (+) side input terminal number of 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC differs from that of 0 to 1 V DC. For the input terminal number, the (+) side for 0 to 5 V DC, 1 to 5 V DC, and 0 to 10 V DC is 9 , and the (+) side for 0 to 1 V DC is 10 . · When using a relay contact output type, externally use a relay according to the capacity of the load to protect the built-in relay contact. · When wiring, keep input wires (thermocouple, RTD, etc.) away from controller AC power sources or load wires.
– 15 –
ટર્મિનલ વ્યવસ્થા

Terminal PWR EV1 EV2 EV3 O2 P24 O1 TC RTD DC CT1 CT2 RS-485 EVENT INPUT
EXT CONT TRANSMIT OUTPUT
(ફિગ. 4.1-1- XNUMX-XNUMX)
Description Power supply voltage Event output 1 Event output 2 (optional: EV2) Event output 3 (optional: EV3) Control output OUT2 (Cooling output) [optional: EV2, O2(SSR/A)] 24 V DC insulated power output (optional: P24) Control output OUT1 or heating output [optional: EV2, O2(SSR/A)] Thermocouple input RTD input Direct current input or DC voltage input CT input 1 (optional: C5W, W) CT input 2 (optional: C5W, W) Serial communication RS-485 (optional: C5W, C5) EI1 (optional: other than C5W) EI2 (optional: other than C5W) EI3 (optional: other than EI, W or C5W) EI4 (optional: other than EI, W or C5W) External setting input (optional: EA) Transmission output (optional: TA, TV)
4.2 લીડ વાયર સોલ્ડરલેસ ટર્મિનલ
ઇન્સ્યુલેશન સ્લીવ સાથે સોલ્ડરલેસ ટર્મિનલનો ઉપયોગ કરો જેમાં નીચે બતાવ્યા પ્રમાણે M3 સ્ક્રૂ બંધબેસે છે.
The torque should be 0.63 N·m.
સોલ્ડરલેસ ટર્મિનલ
ઉત્પાદક
મોડલ
ટોર્કને કડક બનાવવું
Y-પ્રકાર રીંગ-પ્રકાર
નિચિફુ ટર્મિનલ ઇન્ડસ્ટ્રીઝ કો., લિ.
J.S.T.MFG.CO., LTD. NICHIFU TERMINAL INDUSTRIES CO., LTD. J.S.T.MFG.CO., LTD.
TMEX1.25Y-3
VD1.25-B3A TMEX1.25-3 V1.25-3
0.63 N·m
3.2 મીમી
3.2 મીમી
5.8 મીમી મહત્તમ 5.8 મીમી મહત્તમ
(ફિગ. 4.2-1- XNUMX-XNUMX)
– 16 –
4.3 Terminal Cover When using a terminal cover (sold separately), make sure the longer side is on the back right side of the case. Pass the wires from terminals 7 to 12 into the holes of the terminal cover. Terminal cover Mount the longer side of the cover to the back right. (Fig. 4.3-1)
4.4 Wiring For the terminal arrangement, refer to Section `4.1 Terminal Arrangement’ (p.16) 4.4.1 Power Supply Power supply voltage is 100 to 240 V AC or 24 V DC, 48 V DC. For 24 V DC or 48 V DC, ensure polarity is correct.
– 17 –
4.4.2 Control Output OUT1, OUT2 When EV2 or , O2(SSR/A) option is ordered, control output OUT2 is available. Specifications of Control output OUT1, OUT2 are shown below.
Control output OUT1 Relay contact
બિન-સંપર્ક વોલ્યુમtage (for SSR drive) Direct current
ડીસી વોલ્યુમtage
Open collector (NPN)
Control output OUT2 Relay contact
બિન-સંપર્ક વોલ્યુમtage (for SSR drive) Direct current
ડીસી વોલ્યુમtage
1a Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos =0.4) Electrical life: 100, 000 cycles Minimum applicable load: 10 mA 5 V DC 12 V DC 15% Max. 40 mA (short circuit protected) 4 to 20 mA DC, 0 to 20mA DC (Resolution: 12000) Allowable load resistance: Max. 550 0 to 1 V DC, 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC (Resolution: 12000) Allowable load resistance: Max. 1 k Allowable load current: Max. 100 mA Load voltage: Max. 30 V DC Residual voltage: Max. 1.2 V DC Leakage current when OFF: Max. 0.1 mA
1a Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos =0.4) Electrical life: 100, 000 cycles Minimum applicable load: 10 mA 5 V DC 12 V DC 15% Max. 40 mA (short circuit protected) 4 to 20 mA DC, 0 to 20mA DC (Resolution: 12000) Allowable load resistance: Max. 550 0 to 1 V DC, 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC (Resolution: 12000) Allowable load resistance: Max. 1 k
રિલે સંપર્ક
બિન-સંપર્ક વોલ્યુમtage Direct current DC voltage
ઓપન કલેક્ટર
Number of Shinko SSR units when connected in parallel (for Non-contact voltage output): · SA-400 series: 5 units · SA-500 series: 2 units
– 18 –
4.4.3 ઇનપુટ
Each input wiring is shown below. For DC voltage input, (+) side input terminal number of 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC differs from that of 0 to 1 V DC.
થર્મોકોલ
RTD
ડાયરેક્ટ કરંટ, ડીસી વોલ્યુમtage (0 થી 1 V)
ડીસી વોલ્યુમtage
(0 to 5 V, 1 to 5 V, 0 to 10 V)
4.4.4 Event Output 1, Event Output 2, Event Output 3
Event output EV1 is a standard feature. If EV2 option is ordered, Event output EV2 is available. If EV3 option is ordered, Event output EV3 is available. Specifications of Event output 1, Event output 2 and Event output 3 are shown below.
રિલે સંપર્ક
1a Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos =0.4) Electrical life: 100, 000 cycles Minimum applicable load: 10 mA 5 V DC
4.4.5 Insulated Power Output
If P24 option is ordered, the Insulated power output is available.
Specifications of Insulated power output are shown below.
આઉટપુટ વોલ્યુમtage
24 3 V DC (at load current 30 mA DC)
રિપલ વોલ્યુમtage
Within 200 mV DC (at load current 30 mA DC)
મહત્તમ લોડ વર્તમાન
30 એમએ ડીસી
– 19 –
4.4.6 CT Input CT input is available when Heater burnout alarm (C5W, W options) is ordered.
Pass one lead wire of the heater circuit into the hole of the CT. (Fig. 4.4.6-1) When wiring, keep the CT wire away from AC sources or load wires to avoid the external interference.
CT1 input terminals
CT Heater
વીજ પુરવઠો
(ફિગ. 4.4.6-1- XNUMX-XNUMX)
If using 3-phase, pass any 2 lead wires of R, S, T into the CT, and connect them to CT1 ( 13, )14 and CT2 (14, 15) terminals. (Fig. 4.4.6-2)
CT1 input terminals CT2 input terminals
હીટર
સીટી1
R
S Power supply
CT2 T
(ફિગ. 4.4.6-2- XNUMX-XNUMX)
– 20 –
સીરીયલ કોમ્યુનિકેશન

If the C5, C5W (20A) or C5W (100A) option is ordered, Serial communication is available.
(1) Serial Communication When using USB communication cable CMC-001-1 (sold separately)
USB communication cable CMC-001-1 (sold separately)
હોસ્ટ કમ્પ્યુટર યુએસબી પોર્ટ
YYAA((–)) YYBB((++)) CCOOMM
FG
ACS2 YYAA((–)) YYBB((++)) SSGG
શીલ્ડ વાયર
YYSYYSABGABG((((-+-+))))
FG
(ફિગ. 4.4.7-1- XNUMX-XNUMX)
શીલ્ડ વાયર
YYAA((–)) YYBB((++)) SSGG
When using communication converter IF-400 (sold separately)
TXD 3 RXD 2 GND 5 DCD 1 DTR 4
કોમ્યુનિકેશન કન્વર્ટર IF-400 (અલગથી વેચાય છે)
આરએસ- 232C
આરએસ-485
4 4
3 3
1 1
6 6
શીલ્ડ વાયર
FG
ડીએસઆર 6
RTS 7
CTS 8
FG
આરઆઈ 9
હોસ્ટ કમ્પ્યુટર ડી-સબ 9-પિન કનેક્ટર
FG CDM
ACS2 YYAA((–)) YYBB((++)) SSGG
Shield wire YYAA((–)) YYBB((++)) SSGG
શીલ્ડ વાયર
YYAA(-()-) YYBB(+(+) )
SSGG
(ફિગ. 4.4.7-2- XNUMX-XNUMX)
– 21 –
(2) SV digital transmission
Selecting SV digital transmission in the serial communication protocol selection allows digital transmission of the SV when combined with a controller with communication function [Serial Communication (OP: C5, C5W)].
Wiring For the SV digital transmission, connect YA (-) to YA (-), YB (+) to YB (+), SG to SG terminal respectively. Up to 31 units can be connected.
વાયરિંગ ભૂતપૂર્વample of controller with communication function and ACS2
ACS2
YA(-) YB(+)
SG
Shield wire FG
શીલ્ડ વાયર
FG
YA(-) YB(+) SG
YA(-) YB(+) SG
controller with communication function (Up to 31 units)
Shield wire FG
YA(-) YB(+) SG
(ફિગ. 4.4.7-3- XNUMX-XNUMX)
Shield wire Connect only one end of the shield to the FG to avoid a ground loop. If both ends of the shield wire are connected to the FG, the circuit will be closed, resulting in a ground loop. This may cause noise. Be sure to ground the FG. Recommended cable: OTSC-VB 2PX0.5SQ (made by Onamba Co., Ltd.) or equivalent (Use a
twisted pair cable.)
– 22 –
4.4.8 Event Input
4 points (EI1 to EI4) are added as event inputs. For options other than C5W and EI, 2 points (EI1 and EI2) are added simultaneously. The event allocated via the event input allocation selection is executed based on whether the allocated event is in the ON (closed) or OFF (open) state. Specifications of Event input are shown below.
Circuit current when closed Approx. 2.3 mA
EI1, EI2
EI3, EI4
4.4.9 External Setting Input
If the EA option is ordered, External setting input is available. Specifications of External setting input are shown below.
Setting signal
ડાયરેક્ટ કરંટ 4 થી 20 એમએ ડીસી
Allowable input
50 mA DC મહત્તમ
ઇનપુટ અવબાધ
50 મહત્તમ
ઇનપુટ એસampલિંગ અવધિ
100 એમ.એસ
૯.૮ ટ્રાન્સમિશન આઉટપુટ
If the TA and TV options are ordered, Transmission output is available.
Specifications of Transmission output are shown below.
ઠરાવ
12000
આઉટપુટ
4 to 20 mA DC Load resistance: Max 550
0 to 1V DC Load resistance: Max 1 k
0 to 10V DC Load resistance: Max 1 k
આઉટપુટ ચોકસાઈ
ટ્રાન્સમિશન આઉટપુટ સ્પાનના 0.3% ની અંદર
– 23 –
Outline of Key Operation and Each Mode

5.1 key Operation The key operations outline is shown below.
પાવર ચાલુ
(*1)
રન મોડ
PV/SV display mode or
(*2)
Standby mode (Program control)
Program control RUN mode
(*2)
Control output OFFmode
(*2)
મેન્યુઅલ કંટ્રોલ મોડ
Direct setting mode (Main setting)
Setting group mode
Main setting group
Program setting group
AT setting group
PID setting group
Alarm setting group
Input setting group
Output setting group
EVT input setting group
EVToutput setting group
Communication setting group
Transmission output setting group External setting input setting group Control function setting group Program function setting group Wait setting group
Other setting group
Maintenance group
or ( 3 sec)
MV indication mode Remaining time mode
Each setting item (Press the key to move to the next item,
and the key to move to the previous item.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
Each setting item
(Operation is the same as above.)
– 24 –
(*1): Control starts from previous status (last shutdown). (*2): To switch from PV/SV display mode to control output OFF mode or manual control mode, use the or key. (*3): No operation for 2 seconds or pressing the key will return to the PV/SV display mode.
[Key Operation] (3 sec): Press and hold the key for approx. 3 seconds. : Press and hold the and keys together.Settings for each setting item: Use the and keys to change the value, the key to select the digit for numerical input, and the Selection of each selection item: Use the and keys for settings or selections, and register them by pressing the key.
key to register it.
– 25 –
5.2 સ્થિતિઓ
The descriptions of each mode are shown below.
મોડ
વર્ણન
રન મોડ
The PV Display indicates PV, and the SV Display indicates SV.
PV/SV display mode or When the standby mode is active (program control), the PV display
Standby mode (Program indicates the PV. The SV display is off.
નિયંત્રણ)
Control starts from previous status (last shutdown).
To switch from PV/SV display mode to control output OFF mode or manual
control mode, use the or key.
Depending on the function selection for the key or key, the
operation will be as follows:
Function selection for key or key
વર્ણન
કોઈ કાર્ય નથી
It will become no function.
ઓટો/મેન્યુઅલ નિયંત્રણ
Switches the Auto/Manual control.
Control output OFF function Turns the control output ON or OFF.
Remote/Local selection
Switches the Remote/Local.
RUN/STOP function
Switches the RUN/STOP.
Direct setting mode
In PV/SV display mode, pressing the or key switches to Direct
(મુખ્ય સેટિંગ)
setting mode (only during Fix control) to set the SV.
When selecting the set value memory function in Event input allocation
setting, configure SV1 to SV8.
After switching to Direct setting mode, the first digit flashes.
Press the key to advance the digit.
No operation for 2 sec or press key
ચાવી
or
ચાવી
Operations within each setting item
ચાવી
ચાવી
ચાવી
Displayed alternately
Displayed alternately
Displayed alternately
Displayed alternately
MV indication mode Remaining time mode
ચાવી
In PV/SV display mode, press and hold the key for approximately 3 seconds to enter MV indication mode. The PV display shows PV, and the SV display shows MV. The decimal point in the first digit flashes. In MV indication mode, pressing the key switches to Remaining time mode (only during program control). The PV display shows the PV value, and the SV display shows the remaining time.
– 26 –
Mode Setting group mode
વર્ણન
In PV/SV display mode or Standby mode (Program control), pressing the
key switches to Setting group mode.
After switching to Setting group mode, press the key to move to each
setting group, and press the key to move in the opposite direction.
Pressing the key in each setting group item moves to items within that
જૂથ
After moving to items within the group, press the key to move to each
setting item, and press the key to move in the opposite direction.
Press and hold the key while pressing the key to move to each
setting group item within the group.
When changing the selection items for Input type selection, Temperature
unit selection, Event output EV allocation setting, Transmission output
type selection, Control action selection, or Integral/Derivative decimal point
position selection within the group, or when executing Date clear setting or
Program clear setting, the PV display will turn off and [
] દેખાશે
on the SV display due to the large number of items requiring update. Key
operations are disabled while [
] પ્રદર્શિત થાય છે.
Standby mode can transition to Setting group mode in the same manner
as PV/SV display mode from Program control RUN mode. When
transitioning from Setting group mode, it will transition to the mode
immediately preceding the transition.
– 27 –
5.3 Basic Operation after Power-ON After the unit is mounted to the control panel and wiring is completed, operate the unit following the procedure below.
(1) Turn the power supply to the unit ON After power-on, the PV Display shows [
] and the SV Display shows [
] લગભગ માટે
3 seconds. Subsequently, the PV Display shows Input type selection and Temperature unit selection,
while the SV Display shows the Input range high limit value (for thermocouple or RTD inputs) or the
Scaling high limit value (for DC voltage or direct current inputs). (Table 5.3-1)
The control output turns OFF (4 mA for current output), and the transmission output is 4 mA.
Control will then start, indicating the PV on the PV Display and SV on the SV Display. (Table 5.3-1)
Sensor Input K
PV Display SV Display PV Display SV Display
J
R
S
B
E
T
N
PL-
C(W/Re5-26)
Pt100
Pt100
Pt100
4 to 20 mA DC (*1) (*2)
0 to 20 mA DC (*1) (*2)
4 to 20 mA DC (*1) (*3)
0 to 20 mA DC (*1) (*3) 0 to 1 V DC
Scaling high limit value
0 થી 5 વી ડીસી
1 થી 5 વી ડીસી
0 થી 10 વી ડીસી
(*1): Selectable input range and decimal point position.
(*2): It has a built-in receiving resistor (50).
(*3): The separately sold receiving resistor (50) is attached externally.
When power is turned ON, if an error occurs, the following error will be displayed on the PV Display.
ભૂલ
પીવી ડિસ્પ્લે
Non-volatile IC memory error
[] is lit
Internal bus error in the instrument Periodic reset of the instrument (malfunction)
Sensor error (outside high limit range) [
] ફ્લેશિંગ છે
Sensor error (outside low limit range) [
] ફ્લેશિંગ છે
– 28 –
(2) Enter each value Refer to Sections `6. Initial Setting’ (p.34) to `8. Operation and Settings of Standard Functions’ (p.107): Enter each value: Input type, Control method, Direct/Reverse action, SV, PID constants, Event output EV1 allocation, etc.
(3) Turn the load circuit power ON Control starts, so as to reach, and then maintain the control target at the SV.
· Indication Range and Control Range
The indication range and control range for each input are as follows.
ઇનપુટ પ્રકાર
Indication Range and Control Range
Thermocouple (no [Input range low limit 50 (90 )]
દશાંશ બિંદુ)
to [Input range high limit + 50 (90 )]
Thermocouple (with [Input range low limit (Input span × 1 %) ( )]
decimal point), RTD to [Input range high limit + 50.0 (90.0 )]
ડીસી વોલ્યુમtage,
[Scaling low limit Scaling span x 10%]સીધો પ્રવાહ
to [Scaling high limit + Scaling span x 10%]
નિયંત્રણ શ્રેણી
Input range low limit or
Scaling low limit (Direct current, DC voltagઇ ઇનપુટ)
-50 (90 ) or
-( Input span × 1 %) ( ) or
-( Scaling span×10 %)
(ડીસી વોલ્યુમtage, Direct current input)
PV
Input range high limit or
Scaling high limit (Direct current, DC voltagઇ ઇનપુટ)
+50 (90 ) or
+50.0 (90.0 ) or
+( Scaling span×10 %) (DC voltage,
Direct current input)
(ફિગ. 5.3-1- XNUMX-XNUMX)
– 29 –
· Overscale and Underscale
Overscale
The following input range is overscale, and the overscale status flag is set.
However, control operation continues during overscale.
Thermocouple (no decimal point)
Input range high limit to Input range high limit + 50 (90 )
Thermocouple (with decimal point), RTD
Input range high limit to Input range high limit + 50.0 (90.0 )
ડીસી વોલ્યુમtage, ડાયરેક્ટ કરંટ
Scaling high limit to Scaling high limit + (Scaling span × 10 %)
If the scaling high limit is 19999 or higher, [
] is displayed, and the control range extends
up to the scaling high limit + (scaling span × 10%).
ઇનપુટ શ્રેણીમાં
Overscale
નિયંત્રણ શ્રેણી
Input range high limit or
Scaling high limit (DC voltage,
Direct current input)
(ફિગ. 5.3-2- XNUMX-XNUMX)
PV
PV
+ 50 (90 ) or
+ 50.0 (90.0 ) or
+ (Scaling span × 10 %) (DC voltage,
Direct current input)
– 30 –
Underscale The following input range is underscale, and the underscale status flag is set.
However, control operation continues during underscale.
Thermocouple (no decimal point) Input range low limit – 50 (90 ) to Input range low limit
Thermocouple (with decimal point), RTD Input range low limit – (Input span ×1 %) ( ) to Input range low limit
Direct current (4 to 20mA, DC voltage (1 to 5V) input Scaling low limit – (Scaling span × 10 %) to Scaling low limit
Underscale PV
ઇનપુટ શ્રેણીમાં
PV
– 50 (90 ) or
– (Input span × 1 %) ( ) – (Scaling span × 10 %) (Input: 4 to 20 mA DC, 1 to 5 V DC)
નિયંત્રણ શ્રેણી
Input range low limit or
Scaling low limit (DC voltage,
Direct current input)
(ફિગ. 5.3-3- XNUMX-XNUMX)
– 31 –
· Sensor error
Thermocouple input (no decimal point) burnout condition
Below Input range low limit – 50 (90 )
The PV Display will flash [
], and the action selected in Action selection when input errors
occur will be performed.
Above Input range high limit + 50 (90 )
The PV Display will flash [
], and the action selected in Action selection when input errors
occur will be performed.
સેન્સર ભૂલ
Underscale
ઇનપુટ શ્રેણીમાં
Overscale
Sensor error PV
નિયંત્રણ શ્રેણી
PV
– 50 (90 )
Input range low limit
Input range high limit
(ફિગ. 5.3-4- XNUMX-XNUMX)
+ ૬૦૦ (૬૦)
Thermocouple input (with decimal point) and RTD input burnout condition
Below Input range low limit – (Input span × 1 %) ( )
The PV Display will flash [
], and the action selected in Action selection when input errors
occur will be performed.
Above Input range high limit + 50.0 (90.0 )
The PV Display will flash [
], and the action selected in Action selection when input errors
occur will be performed.
સેન્સર ભૂલ
Underscale
ઇનપુટ શ્રેણીમાં
Overscale
Sensor error PV
નિયંત્રણ શ્રેણી
– (Input span × 1 %) ( )
Input range low limit
Input range high limit
(ફિગ. 5.3-5- XNUMX-XNUMX)
PV + 50.0 (90.0 )
– 32 –
ડીસી વોલ્યુમtage, Direct current input burnout condition
Below Scaling low limit – (Scaling span × 10 %)
The PV Display will flash [
], and the control output turns OFF.
Above Scaling high limit + (Scaling span × 10 %)
The PV Display will flash [
], and the control output turns OFF.
સેન્સર ભૂલ
Underscale
ઇનપુટ શ્રેણીમાં
Overscale
Sensor error PV
નિયંત્રણ શ્રેણી
PV
Scaling low limit Scaling high limit
– (Scaling span × 10 %)
+ (Scaling span × 10 %)
(ફિગ. 5.3-6- XNUMX-XNUMX)
However, for 0 to 20 mA, 0 to 1 V, 0 to 5 V, and 0 to 10 V, the measured value corresponds to the input at 0 mA or 0 V.
ઇનપુટ શ્રેણીમાં
Overscale
Sensor error PV
નિયંત્રણ શ્રેણી
Operation selection for input error
PV
Scaling high limit Measurement value at 0 mA or 0 V input
+ (Scaling span × 10 %)
(ફિગ. 5.3-7- XNUMX-XNUMX)
· Cold junction error If the internal cold junction temperature falls below -10 junction error occurs. (When thermocouple input is selected)
(14 ) or exceeds 55
(131 ), a cold
· Internal bus error If there is a fault or other abnormality in the internal circuitry, the control output will turn OFF.
– 33 –
6. પ્રારંભિક સેટિંગ
Setup (setting the Input type, Event output allocation, SV, etc.) should be done before using this controller, according to the user’s conditions. Initial settings are configured in the Setting group mode.
The Setting group mode includes setting groups such as Main setting group, AT setting group, PID setting group, Input setting group, Output setting group, EVT input setting group, EVT output setting group, and Other setting group. The factory default settings for the Setting group mode are as follows. If the user’s specification is the same as the factory default value of this instrument, or if user’s instrument has already been installed in a system, initial settings are not necessary. Proceed to Section `7. Settings’ (p.57).
· Main setting group SV1 setting
સેટિંગ આઇટમ
ફેક્ટરી ડિફોલ્ટ 0
· AT setting group Setting and Selection Item
AT perform/cancel selection
AT action model selection AT bias setting AT gain setting AT hysteresys setting
Factory Default AT cancel Normal AT 20 1.0 0.5
· PID setting group
સેટિંગ આઇટમ
Block1 OUT1 Proportional band setting
10
Block1 OUT1 Integral time setting
200
Block1 OUT1 Derivative time setting
50
Block1 OUT2 Proportional band setting [Option1: EV2, O2(SSR/A)] 10
Block1 OUT2 Integral time setting [Option1: EV2, O2(SSR/A)]
200
Block1OUT2 Derivative time setting [Option1: EV2, O2(SSR/A)]
50
Block1 MV bias setting
0.0
Block1 Overlap/Dead band setting [Option1: EV2, O2(SSR/A)]
0.0
The same applies up to block number 8.
Block8 OUT1 Proportional band setting
10
Block8 OUT1 Integral time setting
200
Block8 OUT1 Derivative time setting
50
Block8 OUT2 Proportional band setting [Option1: EV2, O2(SSR/A)] 10
Block8 OUT2 Integral time setting [Option1: EV2, O2(SSR/A)]
200
Block8 OUT2 Derivative time setting [Option1: EV2, O2(SSR/A)]
50
Block8 MV bias setting
0.0
Block8 Overlap/Dead band setting [Option1: EV2, O2(SSR/A)]
0.0
ફેક્ટરી ડિફોલ્ટ
– 34 –
· Input setting group Setting and Selection Item
Input type selection Temperature unit selection Scaling high limit setting Scaling low limit setting Decimal point position selection Input sampling selection Number of moving average setting Sensor correction coefficient setting Sensor correction setting
PV filter time constant setting
Factory Default K -200 to 1370 Celsius 1370 -200 No decimal point 125 ms 1 1.000 0.0 0.0
· Output setting group Setting and Selection Item
OUT2 output type selection OUT1 proportional cycle setting
OUT1 ON/OFF hysteresis setting OUT1 high limit setting OUT1 low limit setting OUT1 rate of change limit setting OUT2 output type selection [Option1: EV2, O2(SSR/A)] OUT2 cooling method selection [Option1: EV2, O2(SSR/A)] OUT2 proportional cycle setting [Option1: EV2, O2(SSR/A)]
OUT2 ON/OFF hysteresis setting [Option1: EV2, O2(SSR/A)] OUT2 high limit setting [Option1: EV2, O2(SSR/A)] OUT2 low limit setting [Option1: EV2, O2(SSR/A)] Direct/Reverse action selection Pre-set output setting 1 (Option2: except EI or C5W) Pre-set output setting 2 [Option1: EV2, O2(SSR/A)] (Option2: except EI or
C5W)
Operation selection when input error occur OUT1 MV setting when input error occur OUT2 MV setting when input error occur Option1: EV2, O2(SSR/A)]
ફેક્ટરી ડિફોલ્ટ
SSR આઉટપુટ
રિલે સંપર્ક આઉટપુટ:
30.0 સે
બિન-સંપર્ક વોલ્યુમtage output: 3.0 sec
Open collector output: 3.0 sec
1.0
100.0
0.0
0.00
SSR આઉટપુટ
એર ઠંડક
રિલે સંપર્ક આઉટપુટ:
30.0 સે
બિન-સંપર્ક વોલ્યુમtage output: 3.0 sec
કલેક્ટર આઉટપુટ ખોલો:
3.0 સે
1.0
100.0
0.0
વિપરીત ક્રિયા
0.0
0.0
MV when input error occur 0.0 0.0
– 35 –
· EVT input setting group (Option 2: except C5W) Selection Item
Event input EI1 allocation setting Event input EI2 allocation setting Event input EI3 allocation setting Event input EI4 allocation setting
Factory Default No operation No operation No operation No operation
· EVT output setting group Selection Item
Event output EV1 allocation setting Event output EV2 allocation setting (Option1: EV2) (Option1: EV3) Event output EV3 allocation setting (Option1: EV3)
Factory Default No operation No operation No operation
· Communication setting group (Option 2: C5 or C5W) Setting and Selection Item
Communication protocol selection Instrument number setting Communication speed selection Data bit/Parity selection Stop bit selection SVTC
· Transmission output setting group (Option 2: TA) Setting and Selection Item
Transmission output type selection Transmission output high limit setting Transmission output low limit setting
· External setting input setting group (Option 2: EA) Setting and Selection Item
Remote/Local selection External setting input high limit setting External setting input low limit setting Remote bias setting
· Control function setting group Setting and Selection Item
Control action selection Proportional gain 2 DOF coefficient setting Integral 2 DOF coefficient setting Derivative 2 DOF coefficient setting Desired value proportional coefficient setting Gap width setting item Gap coefficient setting item Integral/Derivative decimal point position selection
Factory Default Shinko protocol 0 9600 bps 7 bits/Even 1 bit 0 0
Factory Default PV transmission 1370 -200
Local 1370 -200 0
ફેક્ટરી ડિફોલ્ટ
Factory Default 2 DOF PID control 0.40 1.35 0.00 1.00 0.0 1.0 No decimal point
– 36 –
· Program function setting group
Selection Item Fix control/program control selection
· Other setting group Setting and Selection Item
Set value lock selection SV Rise/Fall rate action selection SV Rise/Fall rate time unit selection SV rise rate setting SV fall rate setting LCD display part selection SV display method selection Indication when control output OFF selection OUT/OFF key function selection PF key function selection Auto/Manual control after power ON selection Indication time setting Non-volatile IC memory saving selection
· Maintenance group Setting and Selection Item
EVT input indication EVT output ON setting OUT1 output setting OUT2 output setting [Option1EV2, O2(SSR/A)] Transmission output setting Data clear Yes/No setting Program clear Yes/No setting
Factory Default Fix control
Factory Default Unlock PV start Minute 0 0 All parts Setting SV OFF indication No function No function Automatic control 00:00 Save
No input OFF 0.0 0.0 0.0 No No
ફેક્ટરી ડિફોલ્ટ
– 37 –
6.1 પાવર-ઑન
After power-on, the PV Display shows [
] and the SV Display shows [
] for approximately 3
seconds. Subsequently, the PV Display shows Input type selection and Temperature unit selection, while
the SV Display shows the Input range high limit value (for thermocouple or RTD inputs) or the Scaling
high limit value (for DC voltage or direct current inputs). (Table 6.1-1)
The control output turns OFF (4 mA for current output), and the transmission output is 4 mA.
Control will then start, indicating the PV on the PV Display and SV on the SV Display.
(કોષ્ટક 6.1-1)
Sensor Input K
PV Display SV Display PV Display SV Display
J
R
S
B
E
T
N
PL-
C(W/Re5-26)
Pt100
Pt100
Pt100
4 to 20mA DC(*1)(*2)
0 to 20mA DC(*1)(*2)
4 to 20mA DC(*1)(*3)
0 to 20mA DC(*1)(*3) 0 to 1V DC
Scaling high limit value
0 થી 5V ડીસી
1 થી 5V ડીસી
0 થી 10V ડીસી
(*1): Selectable input range and decimal point position.
(*2): It has a built-in receiving resistor (50).
(*3): The separately sold receiving resistor (50) is attached externally.
6.2 Basic Operation of Settings To enter each setting mode, refer to the respective setting mode.
In the PV/SV display mode, pressing the key will enter the setting group mode. After entering the setting group mode, press the key to enter to each setting group and the key to enter in the opposite direction. Pressing the key in each setting group item will move to items within that group. When entering to items within a group, press the key to enter to each setting item and the key to move in the opposite direction. Within a group, press the key while holding down the key to enter to each setting group item.
– 38 –
6.3 પ્રારંભિક સેટિંગ
6.3.1 Input Setting Group
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the setting (selection) item name, description, and setting range (selection items).
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Input type selection · Selects an input type from thermocouple (10 types), RTD (2 types), direct current
.
ફેક્ટરી ડિફોલ્ટ મૂલ્ય
To enter the Input Settings group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
input setting group is displayed.
કી દબાવો.
Enter the Input type selection.
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Input type selection · Selects an input type from thermocouple (10 types), RTD (1 types), direct current (4 types) and DC voltage (4 type). · When changing the input from DC voltage to other inputs, remove the sensor connected to this controller first, then change the input. If the input is changed with the sensor connected, the input circuit may break. · When changing an input type, refer to Section “8.9 Items to be Initialized by
Changing Settings” (p.131). · Selection item:
K -200 to 1370 K -200.0 to 800.0 K -200.0 to 400.0 J -200 to 1000 J -200.0 to 400.0 R 0 to 1760 S 0 to 1760 B 0 to 1820 E -200 to 800 T -200.0 to 400.0 N -200 to 1300 PL-II 0 to 1390 C(W/Re5-26) 0 to 2315
– 39 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Pt100 -200.0 to 850.0 Pt100 -200 to 850 Pt100 -100.0 to 100.0 4 to 20 mA DC (*1) -19999 to 19999 0 to 20 mA DC (*1) -19999 to 19999 4 to 20 mA DC (*2) -19999 to 19999 0 to 20 mA DC (*2) -19999 to 19999 0 to 1 V DC -19999 to 19999 0 to 5 V DC -19999 to 19999 1 to 5 V DC -19999 to 19999 0 to 10 V DC -19999 to 19999 Temperature unit selection · Select the temperature sensor units: Celsius or Fahrenheit. · Selection item: Celsius Fahrenheit Scaling high limit setting · Sets scaling high limit value. · Setting range: Scaling low limit value to Input range high limit value Scaling low limit setting · Sets scaling low limit value. · Setting range: Input range low limit value to Scaling high limit value Decimal point position selection · Selects decimal point place. · Selection item: No decimal point 1 digit after decimal point 2 digits after decimal point 3 digits after decimal point 4 digits after decimal point
Available only for DC voltage અને વર્તમાન ઇનપુટ્સ
ઇનપુટ એસampling selection · Selects sampling period. · Selection item:
125 ms 50 ms 10 ms Number of moving average setting · Sets number of times to average fluctuations in input values. · Setting range: 1 to 10
– 40 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
Setting Item, Function, Setting Range Sensor correction coefficient setting
· Sets sensor correction coefficients.
સેટિંગ રેન્જ: 0.000 થી 10.000
Sensor correction setting · Sets sensor correction values.
· Setting range: -100.0 to 100.0 (-180.0 to 180.0 )
ડીસી વોલ્યુમtage, current inputs: -1000 to 1000 PV filter time constant setting
· પીવી ફિલ્ટર સમય સતત સેટ કરે છે.
સેટિંગ રેન્જ: 0.0 થી 10.0 સેકન્ડ
(*1): It has a built-in receiving resistor (50).
(*2): The separately sold receiving resistor (50) is attached externally.
[Number of moving average setting] By averaging values that fluctuate due to noise, the display value is stabilized. Moving average count: 1 to 10 timesPV Without moving average
With moving average
સમય
(ફિગ. 6.3.1-1- XNUMX-XNUMX)
– 41 –
[Sensor correction coefficient setting] The slope of the sensor input value can be set. The slope is set to the value calculated using formula . Correction range: 0.000 to 10.000Y1: Point for correction
X1′: Corrected value for the point to be corrected
Y1′: Point for correction
X1: Point for correction
(ફિગ. 6.3.1-2- XNUMX-XNUMX)
1 1
– –
1 1
=
સેન્સર
કરેક્શન
ગુણાંક
સેટિંગ
[Sensor correction setting] When the temperature at the control point differs from the temperature at the sensor installation point, the PV is shifted to compensate. (This is effective within the input rating range, regardless of the sensor correction value.) Correction range: -100.0 to 100.0 (-180.0 to 180.0 ) DC voltage, current inputs: -1000 to 1000[PV filter time constant setting] A digital 1st low pass filter reduces fluctuations in input values caused by noise. PV filter time constant: 0.0 to 10.0 seconds
PV filter time constant = 0
PV’
PV response after setting the PV filter time constant 0.63×PV’
PV
PV filter time constant setting
સમય
(Fig. 6.3.1-3) – 42 –
6.3.2 EVT Input Setting Group If (Option2: except C5W) is not added, this setting group will not be displayed.
Explanation of setting items: The upper section of the left column shows the PV Display setting character, while the lower right section shows the factory default value for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the selection item name, description, and the selected item.
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Event input EI1 allocation setting · Selects Event input EI1 from Event Input Allocation Table.
.
Factory default value To enter the EVT input setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
EVT input setting group is displayed.
Press the key. Enter the Event input EI1 allocation setting.
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Event input EI1 allocation setting
· Selects Event input EI1 from Event Input Allocation Table.
· પસંદગીની વસ્તુ:
Event Input Allocation Table
Selection Event input
મૂલ્ય
કાર્ય
Input ON (Closed)
Input OFF (Open)
કોઈ ઘટના નથી
મૂલ્ય સેટ કરો
2n
1
(*4) memory
નિયંત્રણ
Control OFF Control ON
(*4) ON/OFF
Direct/Reverse Direct
રિવર્સ
ક્રિયા
ક્રિયા
ક્રિયા
Preset output 1 Preset output Usual control
ચાલુ/બંધ
(*2)
Preset output 2 Preset output Usual control
ચાલુ/બંધ
(*2)
ઓટો/મેન્યુઅલ નિયંત્રણ
મેન્યુઅલ નિયંત્રણ
આપોઆપ નિયંત્રણ
ટીકા
n: 1 to 3(*1)
Control output OFF function Always effective
If sensor is burnt out, the unit maintains control with the preset MV. The unit maintains control with the preset MV. (*3)
– 43 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Remote/Local Remote
સ્થાનિક
Option 2: Adapting
to EA
કાર્યક્રમ
ચલાવો
રોકો
Level action when
નિયંત્રણ
પાવર ચાલુ છે
ચલાવો/રોકો
પ્રોગ્રામ નિયંત્રણ
હોલ્ડિંગ
હોલ્ડિંગ નથી
Holding/Not
હોલ્ડિંગ
કાર્યક્રમ
એડવાન્સ
Usual control
નિયંત્રણ
કાર્ય
એડવાન્સ
કાર્ય
Integral action Integral action Usual
Control continues
હોલ્ડિંગ
હોલ્ડિંગ
અભિન્ન
with the integral
ક્રિયા
value being held.
EV(x) output Latch release Usual
latch selection
કામગીરી
(*1): The MEMO Display shows the value obtained by adding 2n and then
incrementing by 1. If EI1=OFF and EI2=ON, the display shows 3. Event input
numbers are assigned sequentially starting from the smallest number: 20, 21,
and so on. For (Option2: EI), the maximum is 8 points; for (Option2: except
C5W), the maximum is 4 points.
(*2) Output Group Settings: “Preset Output Settings 1, 2”. (Edge Operation)
When multiple event inputs select the same function, an OR determination is
બનાવેલ
(*3) If [Option1: EV2, O2(SSR/A)] is not added, this selection item will not be
પ્રદર્શિત
(*4) When control operation is OFF, only event input assignment selections
અને
સક્ષમ છે.
Event input EI2 allocation setting
· Selects Event input EI2 from Event Input Allocation Table.
· Selection item: Same as the Event input EI1 allocation selection.
Event input EI3 allocation setting
· Selects Event input EI3 from Event Input Allocation Table. · Selection item: Same as the Event input EI1 allocation selection.
Event input EI4 allocation setting
· Selects Event input EI4 from Event Input Allocation Table. · Selection item: Same as the Event input EI1 allocation selection.
– 44 –
[Event input]4 points (EI1 to EI4) will be added as event inputs.
For (Option2: EI), the maximum is 8 points; for (Option2: except C5W), the maximum is 4 points.
When adding (Option2: EI)
When the setting value memory function is set for Event input EI1 allocation setting and Event input
EI2 allocation setting
Connection terminal number
– (EI1)
– (EI2)
Set value memory number
ખોલો
ખોલો
SV1
લઘુ
ખોલો
SV2
ખોલો
લઘુ
SV3
લઘુ
લઘુ
SV4
When the setting value memory function is set for Event input EI1 allocation setting and Event input
EI4 allocation setting
Connection terminal number
– (EI1)
– (EI4)
Set value memory number
ખોલો
ખોલો
SV1
લઘુ
ખોલો
SV2
ખોલો
લઘુ
SV3
લઘુ
લઘુ
SV4
– 45 –
6.3.3 EVT Output Setting Group Only items selected in the Event output EV allocation setting will be displayed.
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the setting (selection) item name, description, and setting range (selection items).
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Event output EV1 allocation setting · Selects Event output EV1 from Event Output Allocation Table.
.
Factory default value To enter the EVT output setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
EVT output setting group is displayed.
કી દબાવો.
Enter the Event output EV1 allocation setting.
– 46 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Event output EV1 allocation setting
· Selects Event output EV1 from Event Output Allocation Table.
· પસંદગીની વસ્તુ:
Event Output Allocation Table
સેટિંગ મૂલ્ય
Event output function
ટીકા
કોઈ ઘટના નથી
Alarm output, High limit alarm
Set in the alarm setting mode.
Alarm output, Low limit alarm
Alarm output, High/Low limits alarm
Alarm output, High/Low limits independent alarm Alarm output, High/Low limit range alarm
Alarm output, High/Low limit range independent alarm
Alarm output, Process high alarm
Alarm output, Process low alarm
Alarm output, High limit with standby alarm
Alarm output, Low limit with standby alarm Alarm output, High/Low limits with standby alarm Alarm output, High/Low limits with standby independent alarm
Heater burnout alarm output Set in the alarm setting mode.
Loop break alarm output
Set in the alarm setting mode.
Time signal output
Turns OFF or ON during Program control, by setting OFF and ON time
within the step set in [Step number].
Output during AT
Turns ON during AT.
Pattern end output
Turns ON when Program control ends, and remains ON until turned OFF.
દૂરસ્થ આઉટપુટ
During serial communication, use bit manipulation of communication command
00D6H to turn it OFF or ON. 20 EV1 output 0: OFF
1: ON 21 EV2 output 0: OFF
1: ON 22 EV3 output 0: OFF
1: ચાલુ
Output added when errors occur
Alarm, heater burnout alarm, sensor error, input error, etc., turns ON when error occurs.
મુખ્ય આઉટપુટ
Selectable when Option1:EV2 is attached
કૂલિંગ આઉટપુટ
Selectable when Option1:EV2 is attached
– 47 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
EV1 enabled/disabled selection when alarm sets 0 · When setting value is 0 (zero), alarm action can be Enabled or Disabled. · Selection item:
અક્ષમ કરેલ સક્ષમ
Displays when selecting
થી
in the Event output EV1 allocation setting.
EV1 hysteresis setting
· Sets EV1 alarm hysteresis.
સેટિંગ રેન્જ: 0.1 થી 1000.0 (0.1 થી 1800.0)
ડીસી વોલ્યુમtage, current inputs: 1 to 10000
Displays when selecting
થી
in the Event output EV1 allocation setting.
EV1 action delay timer setting
· Sets EV1 alarm action delay time.
સેટિંગ રેન્જ: 0 થી 10000 સેકન્ડ
Displays when selecting
થી
in the Event output EV1 allocation setting.
EV1 action Energized/De-energized setting
· Selects Energized/De-energized status for EV1 alarm.
· પસંદગીની વસ્તુ:
એનર્જીડ ડી-એનર્જાઇઝ્ડ
Displays when selecting
થી
in the Event output EV1 allocation setting.
EV1 output latch selection
· Select the hold setting when the EV1 output is ON.
· પસંદગીની વસ્તુ:
અક્ષમ કરેલ સક્ષમ
Displays when selecting
થી
TS1 output step number
· Set the TS1 output step.
સેટિંગ રેન્જ: 1 થી 16
in the Event output EV1 allocation setting.
Displays when selecting
in the Event output EV1 allocation setting.
TS1 OFF time setting
· Set the TS1 OFF time.
સેટિંગ રેન્જ: 00:00 થી 99:59
Displays when selecting
in the Event output EV1 allocation setting.
– 48 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
TS1 ON time setting · Set the TS1 ON time. · Setting range: 00:00 to 99:59
Displays when selecting
in the Event output EV1 allocation setting.
Event output EV2 allocation setting
· Selects Event output EV2 from Event Output Allocation Table.
· Selection item: Same as the Event output EV1 allocation selection.
When (Option1: EV2) is attached, it will be displayed during EVT2 and EVT3.
EV2 enabled/disabled selection when alarm sets 0 · When setting value is 0 (zero), alarm action can be Enabled or Disabled. · Selection item:
અક્ષમ કરેલ સક્ષમ
Displays when selecting
થી
in the Event output EV2 allocation setting.
EV2 hysteresis setting
· Sets EV2 alarm hysteresis.
સેટિંગ રેન્જ: 0.1 થી 1000.0 (0.1 થી 1800.0)
ડીસી વોલ્યુમtage, current inputs: 1 to 10000
Displays when selecting
થી
in the Event output EV2 allocation setting.
EV2 action delay timer setting
· Sets EV2 alarm action delay time.
સેટિંગ રેન્જ: 0 થી 10000 સેકન્ડ
Displays when selecting
થી
in the Event output EV2 allocation setting.
EV2 action Energized/De-energized setting
· Selects Energized/De-energized status for EV2 alarm.
· પસંદગીની વસ્તુ:
ઉત્સાહિત
ડી-એનર્જાઇઝ્ડ
Displays when selecting
થી
in the Event output EV2 allocation setting.
EV2 output latch selection
· Select the hold setting when the EV2 output is ON.
· પસંદગીની વસ્તુ:
અક્ષમ
સક્ષમ
Displays when selecting
થી
in the Event output EV2 allocation setting.
– 49 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
TS2 output step number · Set the TS2 output step. · Setting range: 1 to 16
Displays when selecting
in the Event output EV2 allocation setting.
TS2 OFF time setting
· Set the TS2 OFF time.
સેટિંગ રેન્જ: 00:00 થી 99:59
Displays when selecting
in the Event output EV2 allocation setting.
TS2 ON time setting
· Set the TS2 ON time.
સેટિંગ રેન્જ: 00:00 થી 99:59
Displays when selecting
in the Event output EV2 allocation setting.
Event output EV3 allocation setting
· Selects Event output EV3 from Event Output Allocation Table.
· Selection item: Same as the Event output EV1 allocation selection.
When (Option1: EV3) is attached, it will be displayed during EVT3.
EV3 enabled/disabled selection when alarm sets 0 · When setting value is 0 (zero), alarm action can be Enabled or Disabled. · Selection item:
અક્ષમ
સક્ષમ
Displays when selecting
થી
in the Event output EV3 allocation setting.
EV3 hysteresis setting
· Sets EV3 alarm hysteresis.
સેટિંગ રેન્જ: 0.1 થી 1000.0 (0.1 થી 1800.0)
ડીસી વોલ્યુમtage, current inputs: 1 to 10000
Displays when selecting
થી
in the Event output EV3 allocation setting.
EV3 action delay timer setting
· Sets EV3 alarm action delay time.
સેટિંગ રેન્જ: 0 થી 10000 સેકન્ડ
Displays when selecting
થી
in the Event output EV3 allocation setting.
EV3 action Energized/De-energized setting
· Selects Energized/De-energized status for EV3 alarm.
· પસંદગીની વસ્તુ:
ઉત્સાહિત
ડી-એનર્જાઇઝ્ડ
Displays when selecting
થી
in the Event output EV3 allocation setting.
– 50 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
EV3 output latch selection · Select the hold setting when the EV3 output is ON. · Selection item:
અક્ષમ
સક્ષમ
Displays when selecting
થી
in the Event output EV3 allocation setting.
TS3 output step number · Set the TS3 output step. · Setting range: 1 to 16
Displays when selecting
in the Event output EV3 allocation setting.
TS3 OFF time setting · Set the TS3 OFF time. · Setting range: 00:00 to 99:59
Displays when selecting
in the Event output EV3 allocation setting.
TS3 ON time setting
· Set the TS3 ON time.
સેટિંગ રેન્જ: 00:00 થી 99:59
Displays when selecting
in the Event output EV3 allocation setting.
[Energized/De-energized]જ્યારે
(Energized) is selected, each event output is conductive (ON) while each event output
સૂચક પ્રગટાવવામાં આવે છે.
Each event output is not conductive (OFF) while each event output indicator is not lit.
જ્યારે
(De-energized) is selected, each event output is not conductive (OFF) while each event
output indicator is lit.
Each event output is conductive (ON) while each event output indicator is not lit.
Event output indicator Event output
Energized Lit ON
De-energized Lit OFF
– 51 –
[Loop Break Alarm] Detects control terminal errors (heater burnout, sensor disconnection).When allocated to multiple EVT outputs, the set value is common.
The loop break alarm is evaluated for each loop break alarm time setting; if a normal condition is detected
after an abnormal condition is detected, the alarm is cleared.
Loop break alarm time setting:
0 થી 200 મિનિટ
Loop break alarm band setting: 0 to 150 (0 to 270 )
or 0.0 to 150.0 (0.0 to 270.0 )
ડીસી વોલ્યુમtage, direct current input: 0 to 1500
Loop break alarm dead band setting:
0 થી 150 (0 થી 270)
or 0.0 to 150.0 (0.0 to 270.0 )
ડીસી વોલ્યુમtage, direct current input: 0 to 1500
Alarm detection area
Alarm detection stop area
Alarm detection area
SV
Loop break alarm dead band setting
(ફિગ. 6.3.3-1- XNUMX-XNUMX)
Output: Event output allocated to alarm output in event output setting mode
પસંદગી આઇટમ
પસંદગી
Event output EV allocation setting
: Loop break alarm output
[Time Signal Output]When Time signal output is selected in the Event output allocation setting, during program operation,
when the TS output step occurs, the event output turns ON during the period where TS OFF time
elapsed time (TS OFF time + TS ON time).
પસંદગી આઇટમ
પસંદગી
Event output EV allocation setting
: Time signal output
[Pattern end output]When Pattern end output is selected in the Event output allocation setting, the Pattern end output is
generated after program completion, and [
] flashes on the SV Display. The output turns OFF
when the STOP operation is performed.
પસંદગી આઇટમ
પસંદગી
Event output EV allocation setting
: પેટર્ન એન્ડ આઉટપુટ
[Remote output]When Remote output is selected in the Event output allocation setting, the host can forcibly turn the
output ON or OFF.
પસંદગી આઇટમ
પસંદગી
Event output EV allocation setting
: Remote output
– 52 –
6.3.4 Transmission Output Setting Group If (Option2: TA, TV) is not added, this setting group will not be displayed.
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the setting (selection) item name, description, and setting range (selection items).
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Transmission output type · Selects transmission output type.
.
Factory default value To enter the transmission output setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
transmission output setting group is displayed.
કી દબાવો.
Enter the transmission output setting.
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Transmission output type · Selects transmission output type. · Selection item:
PV transmission SV transmission MV transmission Transmission output high limit setting (for PV and SV transmission) · Sets the Transmission output high limit value. · Setting range: Transmission output low limit setting to High limit input range Transmission output low limit setting (for PV and SV transmission) · Sets the Transmission output low limit value. · Setting range: Low limit input range to Transmission output high limit setting Transmission output high limit setting (for MV transmission) · Sets the Transmission output high limit value. · Setting range: Transmission output low limit setting to 105.0 % Transmission output low limit setting (for MV transmission) · Sets the Transmission output low limit value. · Setting range: -5.0 % to Transmission output high limit setting
– 53 –
6.3.5 External Setting Input Setting Group If (Option2: EA) is not added, this setting group will not be displayed.
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the setting (selection) item name, description, and setting range (selection items).
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Remote/Local selection · Select whether to operate the SV settings remotely (remote operation) or locally
.
Factory default value To enter the external setting input setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
external setting input setting group is displayed.
કી દબાવો.
Enter the remote/Local selection.
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Remote/Local selection · Select whether to operate the SV settings remotely (remote operation) or locally
(key operation). · Selection item:
Local Remote External setting input high limit setting · Set the external setting input high limit value (value when 20 mA DC is input). · Setting range: External setting input low limit setting to High limit input range External setting input low limit setting · Set the external setting input low limit value (value when 4 mA DC is input). · Setting range: Low limit input range to External setting input high limit setting Remote bias setting · During remote action, SV includes the remote bias value. (External setting input low limit to External setting input high limit) · Setting range: 20% of input span
– 54 –
6.3.6 Main Setting Group
Explanation of setting items: The upper section of the left column is the PV Display showing the process value. The lower right section is the SV Display showing the factory default value. The lower left section is the MEMO/STEP Display showing the setpoint memory number. The right column shows the setting item name, description, and setting range.
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
SV1 setting · Set the SV1.
.
Factory default value To enter the main setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
main setting group is displayed.
કી દબાવો.
Enter the SV1 setting.
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
SV1 setting · Set the SV1. · Setting range:
Scaling low limit to Scaling high limit SV2 setting (*1) · Set the SV2. · Setting range:
Scaling low limit to Scaling high limit SV3 setting (*1) · Set the SV3. · Setting range:
Scaling low limit to Scaling high limit SV4 setting (*1) · Set the SV4. · Setting range:
Scaling low limit to Scaling high limit SV5 setting (*2) · Set the SV5. · Setting range:
Scaling low limit to Scaling high limit
– 55 –
Characters,
ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
SV6 setting (*2)
· Set the SV6.
· સેટિંગ રેન્જ:
Scaling low limit to Scaling high limit
SV7 setting (*2)
· Set the SV7.
· સેટિંગ રેન્જ:
Scaling low limit to Scaling high limit
SV8 setting (*2)
· Set the SV8.
· સેટિંગ રેન્જ:
Scaling low limit to Scaling high limit
(*1): If (Option2: C5W) is selected, or if the set value memory function is not selected in the Event
input allocation setting, this setting item will not be displayed.
(*2): If (Option2: EI) is selected, or if the set value memory function is not selected in the Event input
allocation setting, this setting item will not be displayed.
– 56 –
7. સેટિંગ્સ
In this section, each setting group will be explained.
7.1 Main Setting Group
Explanation of setting items: The upper section of the left column shows the PV value on the PV Display, while the lower right section shows the factory default value on the SV Display. The lower left section shows the MEMO/STEP Display, indicating the setpoint memory number. The right column shows the setting item name, description, and setting range.
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
SV1 setting · Set the SV1.
.
Factory default value To enter the main setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
main setting group is displayed.
Press the key. Enter the SV1 setting.
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
SV1 setting · Set the SV1. · Setting range:
Scaling low limit to Scaling high limit SV2 setting (*1) · Set the SV2. · Setting range:
Scaling low limit to Scaling high limit SV3 setting (*1) · Set the SV3. · Setting range:
Scaling low limit to Scaling high limit SV4 setting (*1) · Set the SV4. · Setting range:
Scaling low limit to Scaling high limit SV5 setting (*2) · Set the SV5. · Setting range:
Scaling low limit to Scaling high limit
– 57 –
Characters,
ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
SV6 setting (*2)
· Set the SV6.
· સેટિંગ રેન્જ:
Scaling low limit to Scaling high limit
SV7 setting (*2)
· Set the SV7.
· સેટિંગ રેન્જ:
Scaling low limit to Scaling high limit
SV8 setting (*2)
· Set the SV8.
· સેટિંગ રેન્જ:
Scaling low limit to Scaling high limit
(*1): If (Option2: C5W) is selected, or if the set value memory function is not selected in the Event
input allocation setting, this setting item will not be displayed.
(*2): If (Option2: EI) is selected, or if the set value memory function is not selected in the Event input
allocation setting, this setting item will not be displayed.
– 58 –
7.2 Program Settings Group If program control is selected in the control/program control selection, this setting group will be displayed.
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the program step number for the MEMO/STEP Display. The right column shows the setting item name, description, and setting range.
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Step 1 SV setting · Set the Step 1 SV.
.
Factory default value To enter the program setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
program setting group is displayed.
કી દબાવો.
Enter the Step 1 SV setting item.
– 59 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Step 1 SV setting · Set the Step 1 SV. · Setting range:
Scaling low limit to Scaling high limit Step 1 time setting · Set the Step 1 time. · Setting range:
, 00:00 to 99:59 Step 1 weight block No. setting · Set the weight block No. to be used in Step 1. · Setting range:
1 to 8 Step 1 PID block No. setting · Set the PID block No. to be used in Step 1. · Setting range:
1 to 8 Step 2 SV setting · Set the Step 2 SV. · Setting range:
Scaling low limit to Scaling high limit Step 2 time setting · Set the Step 2 time. · Setting range:
, 00:00 to 99:59 Step 2 weight block No. setting · Set the weight block No. to be used in Step 2. · Setting range:
1 to 8 Step 2 PID block No. setting · Set the PID block No. to be used in Step 2. · Setting range:
1 to 8 Step 3 SV setting · Set the Step 3 SV. · Setting range:
Scaling low limit to Scaling high limit Step 3 time setting · Set the Step 3 time. · Setting range:
, 00:00 to 99:59 Step 3 weight block No. setting · Set the weight block No. to be used in Step 3. · Setting range:
1 to 8 Step 3 PID block No. setting · Set the PID block No. to be used in Step 3. · Setting range:
1 to 8 The same applies up to program step No. 16.
– 60 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Step 16 SV setting · Set the Step 16 SV. · Setting range:
Scaling low limit to Scaling high limit Step 16 time setting · Set the Step 16 time. · Setting range:
, 00:00 to 99:59 Step 16 weight block No. setting · Set the weight block No. to be used in Step 16. · Setting range:
1 to 8 Step 16 PID block No. setting · Set the PID block No. to be used in Step 16. · Setting range:
1 થી 8
– 61 –
7.3 AT Settings Group
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the setting (selection) item name, description, and setting range (selection items).
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
AT Perform/Cancel setting · Auto-tuning is performed in PID control action.
.
Factory default value To enter the AT setting group, follow the steps below.
In PV/SV display mode, press the AT setting group is displayed.
key several times until the character of the
કી દબાવો.
Enter the AT Perform/Cancel setting item.
– 62 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
AT Perform/Cancel setting · Auto-tuning is performed in PID control action.
Press the up key to start auto-tuning, and the down key to cancel it. If auto-tuning does not finish within 4 hours after starting, it will be forcibly terminated. (This is invalid for operations other than PID control action.) · Selection item:
AT cancel AT perform AT action model selection · Select Normal AT, AT on startup, or Fast AT. · Selection item: Normal AT AT on startup Fast AT AT bias setting · Set the bias value that automatically determines the AT point based on the PV/SV deviation (invalid for no PID control action and DC voltage/direct current input). · Setting range: 0 to 50 (0 to 90 ) or 0.0 to 50.0 (0.0 to 90.0 ) AT gain setting · Set the ratio of the proportional band calculated during AT perform. · Setting range: 0.1 to 10.0 AT hysteresis setting · Set the threshold for switching AT from ON to OFF and from OFF to ON. · Setting range: 0.0 to 5.0 (0.0 to 9.0 ) DC voltage, direct current input: 0 to 50
– 63 –
7.4 PID Settings Group
Set the parameters for PID blocks 1 to 8. In the case of fix control, the PID block for SVn is the nth block. n1 to 8
Fix control SVn
PID block n
SV1
PID block1
SV2
PID block2
SV8
PID block8
(1) OUT1 proportional band setting (block n) (2) OUT1 integral time setting (block n) (3) OUT1 derivative time setting (block n) (4) OUT2 proportional band setting (block n) (5) OUT2 integral time setting (block n) (6) OUT2 derivative time setting (block n) (7) MV bias setting (block n) (8) Overlap and deadband setting (block n)
Set the OUT1 proportional band for PID block n. Set the OUT1 integral time for PID block n. Set the OUT1 derivative time for PID block n. Set the OUT2 proportional band for PID block n. Set the OUT2 integral time for PID block n. Set the OUT2 derivative time for PID block n. Set the OUT2 MV bias for PID block n. Set the OUT2 overlap and deadband for PID block n.
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the PID block number for the MEMO/STEP Display. The right column shows the setting item name, description, and setting range.
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Block1 OUT1 proportional band setting · Set the OUT1 proportional band for PID block1.
.
Factory default value To enter the PID setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
PID setting group is displayed.
કી દબાવો.
Enter the Block1 OUT1 proportional band setting item.
– 64 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Block1 OUT1 proportional band setting · Set the OUT1 proportional band for PID block1. · Setting range:
Except when Fast-PID control is selected Input without decimal point: 1 to input span ( ) Input with decimal point: 0.1 to input span ( ) DC voltage, direct current input: 0.1 to 1000.0 %
When Fast-PID control is selected Input without decimal point: 0 to input span ( ) Input with decimal point: 0.0 to input span ( ) DC voltage, direct current input: 0.0 to 1000.0 %
Block1 OUT1 integral time setting · Set the OUT1 integral time for PID block1. · Setting range:
Except when Slow-PID control is selected 0 to 10000 sec or 0.0 to 1999.9 sec
When Slow-PID control is selected 1 to 10000 sec or 0.1 to 1999.9 sec
Block1 OUT1 derivative time setting · Set the OUT1 derivative time for PID block1. · Setting range:
0 to 10000 sec or 0.0 to 1999.9 sec Block1 OUT2 proportional band setting · Set the OUT2 proportional band for PID block1. · Setting range:
0 to input span ( ) or 0.0 to input span ( ) DC voltage, direct current input: 0.0 to 1000.0 %
This setting item will not be displayed except when selecting
allocation setting for [Option1: EV2, O2(SSR/A)].
Block1 OUT2 integral time setting · Set the OUT2 integral time for PID block1. · Setting range:
Except when Slow-PID control is selected 0 to 10000 sec or 0.0 to 1999.9 sec
When Slow-PID control is selected 1 to 10000 sec or 0.1 to 1999.9 sec
Block1 OUT2 derivative time setting · Set the OUT2 derivative time for PID block1. · Setting range:
0 to 10000 sec or 0.0 to 1999.9 sec Block1 MV bias setting · Set the MV bias for PID block1. · Setting range:
0.0 થી 100.0 %
(OUT2) in the Event output EV2
– 65 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Block1 Overlap and deadband setting · Set the overlap and deadband for PID block1. · Setting range:
-100.0 to 100.0 (-180.0 to 180.0 ) DC voltage, direct current input: -1000 to 1000
This setting item will not be displayed except when selecting
allocation setting for [Option1: EV2, O2(SSR/A)].
The same applies up to block No. 8. Block8 OUT1 proportional band setting · Set the OUT1 proportional band for PID block8. · Setting range:
Except when Fast-PID control is selected Input without decimal point: 1 to input span ( ) Input with decimal point: 0.1 to input span ( ) DC voltage, direct current input: 0.1 to 1000.0 %
When Fast-PID control is selected Input without decimal point: 0 to input span ( ) Input with decimal point: 0.0 to input span ( ) DC voltage, direct current input: 0.0 to 1000.0 %
Block8 OUT1 integral time setting · Set the OUT1 integral time for PID block8. · Setting range:
Except when Slow-PID control is selected 0 to 10000 sec or 0.0 to 1999.9 sec
When Slow-PID control is selected 1 to 10000 sec or 0.1 to 1999.9 sec
Block8 OUT1 derivative time setting · Set the OUT1 derivative time for PID block8. · Setting range: 0 to 10000 sec or 0.0 to 1999.9 sec Block8 OUT2 proportional band setting · Set the OUT2 proportional band for PID block8. · Setting range:
0 to input span ( ) or 0.0 to input span ( ) DC voltage, direct current input: 0.0 to 1000.0 %
This setting item will not be displayed except when selecting
allocation setting for [Option1: EV2, O2(SSR/A)].
Block8 OUT2 integral time setting · Set the OUT2 integral time for PID block8. · Setting range:
Except when Slow-PID control is selected 0 to 10000 sec or 0.0 to 1999.9 sec
When Slow-PID control is selected 1 to 10000 sec or 0.1 to 1999.9 sec
(OUT2) in the Event output EV2 (OUT2) in the Event output EV2
– 66 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Block8 OUT2 derivative time setting · Set the OUT2 derivative time for PID block8. · Setting range: 0 to 10000 sec or 0.0 to 1999.9 sec Block8 MV bias setting · Set the MV bias for PID block8. · Setting range: 0.0 to 100.0 % Block8 Overlap and deadband setting · Set the overlap and deadband for PID block8. · Setting range:
-100.0 to 100.0 (-180.0 to 180.0 ) DC voltage, direct current input: -1000 to 1000
This setting item will not be displayed except when selecting
allocation setting for [Option1: EV2, O2(SSR/A)].
(OUT2) in the Event output EV2
– 67 –
7.5 Alarm Setting Group
If selecting alarm actions (
થી
), heater burnout alarm (
), and loop break alarm
(
) in the Event output EV allocation setting, this setting group will be displayed.
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the setting item name, description, and setting range.
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
EV1 alarm value · Set the EV1 alarm setting.
.
Factory default value To enter the alarm setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
alarm setting group is displayed.
કી દબાવો.
Enter the EV1 alarm value item.
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
EV1 alarm value
· Set the EV1 alarm setting.
This is displayed when selecting an alarm action in the Event output EV1
allocation setting.
પસંદ કરતી વખતે
(Alarm output High/Low limits independent alarm) in the
Event output EV1 allocation setting, set the low limit action point for the EV1
એલાર્મ
· પસંદગીની વસ્તુ:
કોઈ ક્રિયા નથી
ઉચ્ચ મર્યાદા એલાર્મ
-(Input span) to Input span (*1)
ઓછી મર્યાદા એલાર્મ
-(Input span) to Input span (*1)
ઉચ્ચ/નીચી મર્યાદા એલાર્મ
0 to Input span (*1)
High/Low limits independent alarm
0 to Input span (*1)
ઉચ્ચ/નીચી મર્યાદા શ્રેણી એલાર્મ
0 to Input span (*1)
High/Low limit range independent alarm
0 to Input span (*1)
ઉચ્ચ એલાર્મની પ્રક્રિયા કરો
Input range low limit to Input range high limit (*2)
લો એલાર્મ પર પ્રક્રિયા કરો
Input range low limit to Input range high limit (*2)
સ્ટેન્ડબાય એલાર્મ સાથે ઉચ્ચ મર્યાદા
-(Input span) to Input span (*1)
સ્ટેન્ડબાય એલાર્મ સાથે ઓછી મર્યાદા
-(Input span) to Input span (*1)
સ્ટેન્ડબાય એલાર્મ સાથે ઉચ્ચ/નીચી મર્યાદા
0 to Input span (*1)
High/Low limits with standby independent alarm 0 to Input span (*1)
(*1): For DC voltage and direct current inputs, this is the scaling range. (Maximum setting: -19999 to 19999)
(*2): For DC voltage and direct current inputs, this is the scaling low limit (high limit). (Maximum setting: -19999 to 19999)
– 68 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
Mode character and CT1 current value are alternately indicated (0.5 sec cycle).
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
EV1 high limit alarm value
· Set the EV1 high limit alarm value.
પસંદ કરતી વખતે
(Alarm output High/Low limits independent alarm) in the
Event output EV1 allocation setting, set the low limit action point for the EV1
એલાર્મ
· Selection item: Same as those of EV1 alarm value.
EV2 alarm value
· Set the EV2 alarm setting.
This is displayed when selecting an alarm action in the Event output EV2
allocation setting.
પસંદ કરતી વખતે
(Alarm output High/Low limits independent alarm) in the
Event output EV2 allocation setting, set the low limit action point for the EV2
એલાર્મ
· Selection item: Same as those of EV1 alarm value.
This setting item will be displayed, when adding (Option1: EV2, EV3) and selecting alarm actions
થી
in the Event output EV allocation setting.
EV2 high limit alarm value
· Set the EV2 high limit alarm value.
પસંદ કરતી વખતે
(Alarm output High/Low limits independent alarm) in the
Event output EV2 allocation setting, set the low limit action point for the EV2
એલાર્મ
· Selection item: Same as those of EV1 alarm value.
This setting item will be displayed, when adding (Option1: EV2, EV3) and selecting alarm actions
થી
in the Event output EV allocation setting.
EV3 alarm value
· Set the EV3 alarm setting.
This is displayed when selecting an alarm action in the Event output EV3
allocation setting.
પસંદ કરતી વખતે
(Alarm output High/Low limits independent alarm) in the
Event output EV3 allocation setting, set the low limit action point for the EV3
એલાર્મ
· Selection item: Same as those of EV1 alarm value.EVT3Alarm action
This setting item will be displayed, when adding (Option1: EV3).
EV3 high limit alarm value · Set the EV3 high limit alarm value.
પસંદ કરતી વખતે
(Alarm output High/Low limits independent alarm) in the
Event output EV3 allocation setting, set the low limit action point for the EV3
alarm. · Selection item: Same as those of EV1 alarm value.
This setting item will be displayed, when adding (Option1: EV3).
Heater burnout alarm 1 value
· Set the heater current value for Heater burnout alarm 1.
Mode characters and CT1 current value are indicated alternately.
· સેટિંગ રેન્જ:
0.0 to 20.0 A (Option: W20)
0.0 to 100.0 A (Option: W100)
This setting item will be displayed, when adding [Option2: C5W(20A), C5W(100A), W(20A), W(100A)] and
selecting heater burnout alarm
in the Event output EV allocation setting.
– 69 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
Mode character and CT2 current value are alternately indicated (0.5 sec cycle).
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Heater burnout alarm 2 value
· Se the heater current value for Heater burnout alarm 2.
Mode characters and CT2 current value are indicated alternately.
· સેટિંગ રેન્જ:
0.0 to 20.0 A (Option: W20)
0.0 to 100.0 A (Option: W100)
This setting item will be displayed, when adding [Option2: C5W(20A), C5W(100A), W(20A), W(100A)] and
selecting heater burnout alarm
in the Event output EV allocation setting.
Loop break alarm time setting · Set the time to assess the Loop break alarm.
· Setting range: 0 to 200 min
This setting item will be displayed, when adding [Option2: C5W(20A), C5W(100A), W(20A), W(100A)] and
selecting loop break alarm
in the Event output EV allocation setting.
Loop break alarm band setting · Set the temperature to assess the Loop break alarm.
· સેટિંગ રેન્જ:
0 to 150 (0 to 270 ) or 0.0 to 150.0 (0.0 to 270.0 )
ડીસી વોલ્યુમtage, current inputs: 0 to 1500
This setting item will be displayed, when selecting loop break alarm
in the Event output EV
allocation setting.
Loop break alarm dead band setting · Set the temperature to assess the Loop break alarm dead band.
· સેટિંગ રેન્જ:
0 to 150 (0 to 270 ) or 0.0 to 150.0 (0.0 to 270.0 )
ડીસી વોલ્યુમtage, current inputs: 0 to 1500
This setting item will be displayed, when selecting loop break alarm
in the Event output EV
allocation setting.
– 70 –
7.6 Input Setting Group
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the MEMO/STEP Display, where is off. The right column shows the setting (selection) item name, description, and setting range (selection items).
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Input type selection · Select the input type from thermocouple (10 types), RTD (1 type), direct current
.
Factory default value To enter the input setting group, follow the steps below.
In PV/SV display mode, press the input setting group is displayed.
key several times until the character of the
કી દબાવો.
Enter the input type selection item.
– 71 –
Characters,
ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Input type selection · Select the input type from thermocouple (10 types), RTD (1 type), direct current
(4 types) and DC voltage (4 type), and the unit / . · When changing the input from DC voltage અન્ય ઇનપુટ્સ માટે, સેન્સરને દૂર કરો
connected to this controller first, then change the input. If the input is changed with the sensor connected, the input circuit may break. · When changing an input type, refer to Section “8.9 Items to be Initialized by Changing Settings” (p.131). · Selection item:
K-200 થી 1370
K-200.0 થી 800.0
K-200.0 થી 400.0
જે-200 થી 1000
જે-200.0 થી 400.0
આર 0 થી 1760
એસ 0 થી 1760
બી 0 થી 1820
ઇ -200 થી 800
ટી -200.0 થી 400.0
એન -200 થી 1300
PL-II 0 to 1390
C(W/Re5-26) 0 થી 2315
Pt100 -200.0 થી 850.0
Pt100 -200 થી 850
Pt100 -100.0 થી 100.0
4 to 20 mA DC (*1) -19999 to 19999
0 to 20 mA DC (*1) -19999 to 19999
4 to 20 mA DC (*2) -19999 to 19999
0 to 20 mA DC (*2) -19999 to 19999
0 થી 1 વી ડીસી -19999 થી 19999
0 થી 5 વી ડીસી -19999 થી 19999
1 થી 5 વી ડીસી -19999 થી 19999
0 થી 10 વી ડીસી -19999 થી 19999
(*1): It has a built-in receiving resistor (50).
(*2): The separately sold receiving resistor (50) is attached externally.
– 72 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Temperature unit selection · Select the temperature sensor units: Celsius or Fahrenheit. · Selection item:
Celsius Fahrenheit Scaling high limit setting · Sets scaling high limit value. · Setting range: Scaling low limit value to Input range high limit value Scaling low limit setting · Sets scaling low limit value. · Setting range: Input range low limit value to Scaling high limit value Decimal point position selection · Selects decimal point place. · Selection item: No decimal point 1 digit after decimal point 2 digits after decimal point 3 digits after decimal point 4 digits after decimal point
Available only for DC voltage અને વર્તમાન ઇનપુટ્સ
ઇનપુટ એસampling selection · Selects sampling period. · Selection item:
125 ms 50 ms 10 ms Number of moving average setting · Sets number of times to average fluctuations in input values. · Setting range: 1 to 10 Sensor correction coefficient setting · Sets sensor correction coefficients. · Setting range: 0.000 to 10.000 Sensor correction setting · Sets sensor correction values. · Setting range: -100.0 to 100.0 (-180.0 to 180.0 ) DC voltage, current inputs: -1000 to 1000 PV filter time constant setting · Sets PV filter time constant. · Setting range: 0.0 to 10.0 seconds
– 73 –
[Number of moving average setting] By averaging values that fluctuate due to noise, the display value is stabilized. Moving average count: 1 to 10 timesPV Without moving average
With moving average
સમય
(Fig. 7.6-1) [Sensor correction coefficient setting] The slope of the sensor input value can be set. The slope is set to the value calculated using formula . Correction range: 0.000 to 10.000
Y1: Point for correction
X1′: Corrected value for the point to be corrected
Y1′: Point for correction
X1: Point for correction
(ફિગ. 7.6-2- XNUMX-XNUMX)
1 1
– –
1 1
=
સેન્સર
કરેક્શન
ગુણાંક
સેટિંગ
[Sensor correction setting] When the temperature at the control point differs from the temperature at the sensor installation point, the PV is shifted to compensate. (This is effective within the input rating range, regardless of the sensor correction value.) Correction range: -100.0 to 100.0 (-180.0 to 180.0 ) DC voltage, current inputs: -1000 to 1000– 74 –
[PV filter time constant setting] A digital 1st low pass filter reduces fluctuations in input values caused by noise. PV filter time constant: 0.0 to 10.0 secondsPV filter time constant = 0
PV’
PV response after setting the PV filter time constant 0.63×PV’
PV
PV filter time constant setting
(ફિગ. 7.6-3- XNUMX-XNUMX)
સમય
– 75 –
7.7 Output Setting Group
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the setting (selection) item name, description, and setting range (selection items).
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
OUT1 output type selection · When selecting multi-output, the OUT1 output can be selected from SSR output,
.
ફેક્ટરી ડિફોલ્ટ મૂલ્ય
To enter the output setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
output setting group is displayed.
કી દબાવો.
Enter the input type selection item.
– 76 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
Factory default setting · For relay contact
output type: 30.0 sec · For solid-state
વોલ્યુમtage output type, open collector type: 3.0 sec
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
OUT1 output type selection · When selecting multi-output, the OUT1 output can be selected from SSR output,
direct current output 4 to 20mA, or 0 to 20mA. · Selection item:
SSR output Direct current output (4 to 20 mA DC) Direct current output (0 to 20 mA DC) OUT1 proportional cycle setting · Set the OUT1 proportional cycle. · Setting range: 0.1 to 120.0 sec
This item is not displayed when the direct current/DC voltage output type is set/selected.
OUT1 ON/OFF hysteresis setting · Set the OUT1 ON/OFF hysteresis. · Setting range: 0.1 to 1000.0 (0.1 to 1800.0 )
ડીસી વોલ્યુમtage, current inputs: 1 to 10000 OUT1 high limit setting · Set the OUT1 high limit. · Setting range: Output low limit setting to 100.0 %
ડીસી વોલ્યુમtage, current inputs: Output low limit setting to 105.0 % OUT1 low limit setting · Set the OUT1 low limit. · Setting range: 0.0 to OUT1 high limit setting
ડીસી વોલ્યુમtage, current inputs: -5.0 % to OUT1 high limit setting OUT1 rate of change limit setting · Set the changing value of OUT1 MV for 1 second. · Setting range: 0.00 to 100.00 %/sec OUT2 output type selection · When selecting multi-output, the OUT2 output can be selected from SSR output,
direct current output 4 to 20mA, or 0 to 20mA. · Selection item:
SSR output Direct current output (4 to 20 mA DC) Direct current output (0 to 20 mA DC)
This selection item will not be displayed, when [Option 1: O2(SSR/A)] is not added.
– 77 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
Factory default setting · For relay contact
output type: 30.0 sec · For solid-state
વોલ્યુમtage output type, open collector type: 3.0 sec
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
OUT2 cooling method selection · Select the OUT2 cooling method from air, oil or water cooling. · Selection item:
Air cooling Oil cooling Water cooling
This selection item will not be displayed, when [Option 1: EV2, O2(SSR/A)] is not added.
OUT2 proportional cycle setting · Set the OUT2 proportional cycle. · Setting range: 0.1 to 120.0 sec
This item is not displayed, when [Option 1: EV2, O2(SSR/A)] is not added. This item is not displayed, when the direct current/DC voltage output type is set/selected.
OUT2 ON/OFF hysteresis setting · Set the OUT2 ON/OFF hysteresis. · Setting range: 0.1 to 1000.0 (0.1 to 1800.0 )
ડીસી વોલ્યુમtage, current inputs: 1 to 10000
This selection item will not be displayed, when [Option 1: EV2, O2(SSR/A)] is not added.
OUT2 high limit setting · Set the OUT2 high limit. · Setting range: Output low limit setting to 100.0 %
ડીસી વોલ્યુમtage, current inputs: Output low limit setting to 105.0 %
This selection item will not be displayed, when [Option 1: EV2, O2(SSR/A)] is not added.
OUT2 low limit setting · Set the OUT2 low limit. · Setting range: 0.0 to OUT2 high limit setting
ડીસી વોલ્યુમtage, current inputs: -5.0 % to OUT2 high limit setting
This selection item will not be displayed, when [Option 1: EV2, O2(SSR/A)] is not added.
Direct/Reverse action selection · Selects either Reverse (Heating) or Direct (Cooling) control action. · Selection item:
Reverse (Heating) action Direct (Cooling) action Pre-set output setting 1 · Set the OUT1 MV output when selecting Pre-set output setting 1 or 2 in the Event input allocation setting. · Setting range: -5.0 to 105.0 %
This selection item will not be displayed, when [Option 1: except EI or C5W] is not added.
– 78 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Pre-set output setting 2 · Set the OUT2 MV output when selecting Pre-set output setting 1 or 2 in the Event
input allocation setting.
· Setting range: -5.0 to 105.0 %
This item is not displayed, when [Option 1: EV2, O2(SSR/A)] is not added. This item will not be displayed, when [Option 2: except EI or C5W] is not added.
Action selection when input errors occur · Select the output state for OUT1 and OUT2 when input error occurs.
· પસંદગીની વસ્તુ:
MV setting when input errors occur
Control operation continues OUT1 MV setting when input errors occur · Set the MV to output when an input error occurs.
· Setting range: -5.0 to 105.0 %
This item is displayed when MV setting when input errors occur is selected in Action selection when input errors occur.
OUT1 MV setting when input errors occur · Set the MV to output when an input error occurs.
· Setting range: -5.0 to 105.0 %
This item is displayed when MV setting when input errors occur is selected in Action selection when input errors occur. This item is not displayed, when [Option 1: EV2, O2(SSR/A)] is not added.
When ON-OFF operation: 0%
Output high limit setting and
Output low limit setting
PID calculation
Output rate of change limit
સેટિંગ
MV bias setting
મેન્યુઅલ મોડ
When input errors occur
Control output ON/OFF setting
મેન્યુઅલ MV
MV setting when input errors occur
MV when communication
વાંચન
When 0 is selected in the Control selection when input errors occur
(ફિગ. 7.7-1- XNUMX-XNUMX)
– 79 –
7.8 EVT Input Setting Group If (Option 2: except C5W) is not added, this setting group will not be displayed.
Explanation of setting items: The upper section of the left column shows the PV Display setting character, while the lower right section shows the factory default value for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the selection item name, description, and the selected item.
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Event input EI1 allocation setting · Selects Event input EI1 from Event Input Allocation Table.
.
ફેક્ટરી ડિફોલ્ટ મૂલ્ય
To enter the EVT input setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
EVT input setting group is displayed.
કી દબાવો.
Enter the Event input EI1 allocation setting item.
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Event input EI1 allocation setting
· Selects Event input EI1 from Event input allocation table.
· પસંદગીની વસ્તુ:
Event input allocation table
Selection Event input
ઇનપુટ ચાલુ
મૂલ્ય
કાર્ય
(બંધ)
Input OFF (Open)
કોઈ ઘટના નથી
મૂલ્ય સેટ કરો
2n
1
(*4) memory
નિયંત્રણ
Control OFF Control ON
(*4)
ON/OFF (*2)
Direct/Reverse Direct action Reverse
ક્રિયા
ક્રિયા
Preset output Preset output Usual control
1
(*2)
ચાલુ/બંધ
Preset output Preset output
2
(*2)
ચાલુ/બંધ
Auto/Manual Manual
નિયંત્રણ
નિયંત્રણ
– 80 –
Usual control
આપોઆપ નિયંત્રણ
ટીકા
n: 1 to 3(*1)
Control output OFF function Always effective
If sensor is burnt out, the unit maintains control with the preset MV. The unit maintains control with the preset MV. (*3)
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Remote/Local Remote
સ્થાનિક
Adapt to Option2:
EA
કાર્યક્રમ
ચલાવો
રોકો
Level action when
નિયંત્રણ
પાવર ચાલુ છે
ચલાવો/રોકો
પ્રોગ્રામ નિયંત્રણ
પકડી રાખો
હોલ્ડિંગ નથી
Holding/Not
હોલ્ડિંગ
કાર્યક્રમ
એડવાન્સ
Usual control
નિયંત્રણ
એડવાન્સ
કાર્ય
Integral action Integral action Usual
Control continues
હોલ્ડિંગ
હોલ્ડિંગ
integral action with the integral
value being held.
EV(x) output Latch cancel Usual control
latch selection
(*1): The MEMO Display shows the value obtained by adding 2n and then incrementing by 1. If EI1=OFF and EI2=ON, the display shows 3. Event input numbers are assigned sequentially starting from the smallest number: 20, 21, and so on. For (Option 2: EI), the maximum is 8 points. For (Option 2: except C5W), the maximum is 4 points.
(*2): This corresponds to “Preset Output Settings 1 and 2” in the output group settings. (Edge operation) If multiple event inputs select the same function, an OR determination will be made.
(*3): If [Option 1: EV2, O2(SSR/A)] is not added, this selection item will not be displayed.
(*4): When control operation is OFF, only Event input allocation setting
, અને
Event input EI2 allocation setting
· Selects Event input EI2 from Event Input Allocation Table.
· Selection item: Same as Event input EI1 allocation setting.
Event input EI3 allocation setting
· Selects Event input EI3 from Event Input Allocation Table.
· Selection item: Same as Event input EI1 allocation setting.
Event input EI4 allocation setting
· Selects Event input EI4 from Event Input Allocation Table.
· પસંદગીની વસ્તુ:
Same as Event input EI1 allocation setting.
સક્ષમ છે.
[Event input] 4 points (EI1 to EI4) will be added as event inputs. For (Option 2: EI), the maximum is 8 points; for (Option 2: C5W, except EI), the maximum is 4 points.– 81 –
When adding (Option 2: EI)
When Set value memory is set for Event input EI1 allocation setting and Event input EI2 allocation
સેટિંગ
Connection terminal No.
– (EI1)
– (EI2)
Setting value memory No.
ખોલો
ખોલો
SV1
લઘુ
ખોલો
SV2
ખોલો
લઘુ
SV3
લઘુ
લઘુ
SV4
When Set value memory is set for Event input EI1 allocation setting and Event input EI4 allocation setting
Connection terminal No.
– (EI1)
– (EI4)
ખોલો
ખોલો
લઘુ
ખોલો
ખોલો
લઘુ
લઘુ
લઘુ
Setting value memory No.
SV1 SV2 SV3 SV4
– 82 –
7.9 EVT Output Setting Group Only items selected in the Event output EV allocation setting will be displayed.
Explanation of setting items: The upper section of the left column shows the setting item characters for the PV Display, while the lower right section shows the factory default values for the SV Display. The lower left section shows the MEMO/STEP Display, which is off. The right column shows the setting (selection) item name, description, and setting range (selection items).
MEMO/STEP Display
Setting characters
Setting item name, function, setting range (or selection item)
Event output EV1 allocation setting · Selects Event output EI1 from Event output allocation table.
.
Factory default value To enter the EVT output setting group, follow the steps below.
In PV/SV display mode, press the key several times until the character of the
EVT output setting group is displayed.
કી દબાવો.
Enter the Event input EI2 allocation setting item.
– 83 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Event output EV1 allocation setting
· Selects Event output EV1 from Event output allocation table.
· પસંદગીની વસ્તુ:
Event output allocation table
Selection value
Event output function
ટીકા
કોઈ ઘટના નથી
Alarm output, High limit alarm
Set in alarm setting mode.
Alarm output, Low limit alarm
Alarm output, High/Low limits alarm
Alarm output, High/Low limits
independent alarm
Alarm output, High/Low limit range alarm Alarm output, High/Low limit range independent alarm
Alarm output, Process high alarm
Alarm output, Process low alarm
Alarm output, High limit with standby alarm
Alarm output, Low limit with standby alarm
Alarm output, High/Low limits with standby alarm
Alarm output, High/Low limits with standby independent alarm
Heater burnout alarm output
Set in alarm setting mode.
Loop break alarm output
Set in alarm setting mode.
Time signal output
Turns OFF or ON during Program
control, by setting OFF and ON times
within the step set in [Step number].
Output during AT
Turns ON during AT.
Pattern end output
Turns ON when Program control ends,
and remains ON until turned OFF.
દૂરસ્થ આઉટપુટ
Turns OFF or ON by communication command 00D6H during Serial communication.
20 EV1 output 0: OFF 1: ON
21 EV2 output 0: OFF 1: ON
22 EV3 output 0: OFF 1: ON
Additional output when error occurs Alarm, heater burnout alarm, sensor
error, input error, etc., turns ON when
ભૂલ થાય છે.
મુખ્ય આઉટપુટ
Selectable when Option1: EV2 is
ઉમેર્યું
કૂલિંગ આઉટપુટ
Selectable when Option1: EV2 is
ઉમેર્યું
– 84 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
EV1 enabled/disabled selection when alarm sets 0 · When alarm value is 0 (zero), alarm action can be Enabled or Disabled. · Selection item:
અક્ષમ
સક્ષમ
This setting item will be displayed, when selecting alarm actions
થી
in the Event output
EV1 allocation setting.
EV1 hysteresis setting
· Sets EV1 alarm hysteresis.
સેટિંગ રેન્જ: 0.1 થી 1000.0 (0.1 થી 1800.0)
ડીસી વોલ્યુમtage, current inputs: 1 to 10000
This setting item will be displayed, when selecting
થી
in the Event output EV1 allocation
સેટિંગ
EV1 action delay timer setting
· Sets EV1 alarm action delay time.
સેટિંગ રેન્જ: 0 થી 10000
This setting item will be displayed, when selecting
થી
in the Event output EV1 allocation
સેટિંગ
EV1 action Energized/De-energized setting
· Selects Energized/De-energized status for EV1 alarm.
· પસંદગીની વસ્તુ:
ઉત્સાહિત
ડી-એનર્જાઇઝ્ડ
This setting item will be displayed, when selecting
થી
in the Event output EV1 allocation
સેટિંગ
EV1 output latch selection
· Selects hold when EV1 output is ON.
· પસંદગીની વસ્તુ:
અક્ષમ
સક્ષમ
This setting item will be displayed, when selecting alarm actions
થી
in the Event output
EV1 allocation setting.
TS1 output step number
· Sets TS1 output step number.
સેટિંગ રેન્જ: 1 થી 16
This setting item will be displayed, when selecting
in the Event output EV1 allocation setting.
TS1 OFF time setting · Sets TS1 OFF time setting. · Setting range: 00:00 to 99:59
This setting item will be displayed, when selecting
in the Event output EV1 allocation setting.
TS1 ON time setting · Sets TS1 ON time setting. · Setting range: 00:00 to 99:59
This setting item will be displayed, when selecting
in the Event output EV1 allocation setting.
– 85 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Event output EV2 allocation setting · Selects Event output EV2 from Event output allocation table. · Selection item: Same as the Event output EV1 allocation setting
When (Option 1: EV2) is attached, it will be displayed during EVT2 and EVT3.
EV2 enabled/disabled selection when alarm sets 0
· When alarm value is 0 (zero), alarm action can be Enabled or Disabled.
· પસંદગીની વસ્તુ:
અક્ષમ
સક્ષમ
This setting item will be displayed, when selecting alarm actions
થી
in the Event output
EV2 allocation setting.
EV2 hysteresis setting
· Sets EV2 alarm hysteresis.
સેટિંગ રેન્જ: 0.1 થી 1000.0 (0.1 થી 1800.0)
ડીસી વોલ્યુમtage, current inputs: 1 to 10000
This setting item will be displayed, when selecting
થી
in the Event output EV2 allocation
સેટિંગ
EV2 action delay timer setting
· Sets EV2 alarm action delay time.
સેટિંગ રેન્જ: 0 થી 10000
This setting item will be displayed, when selecting
થી
સેટિંગ
EV2 action Energized/De-energized setting
in the Event output EV2 allocation
· Selects Energized/De-energized status for EV2 alarm.
· પસંદગીની વસ્તુ:
ઉત્સાહિત
ડી-એનર્જાઇઝ્ડ
This setting item will be displayed, when selecting
થી
in the Event output EV2 allocation
સેટિંગ
EV2 output latch selection
· Selects hold when EV2 output is ON.
· પસંદગીની વસ્તુ:
અક્ષમ
સક્ષમ
This setting item will be displayed, when selecting setting.
TS2 output step number · Sets TS2 output step number.
સેટિંગ રેન્જ: 1 થી 16
This setting item will be displayed, when selecting
TS2 OFF time setting · Sets TS2 OFF time setting.
સેટિંગ રેન્જ: 00:00 થી 99:59
This setting item will be displayed, when selecting
TS2 ON time setting · Sets TS2 ON time setting.
સેટિંગ રેન્જ: 00:00 થી 99:59
This setting item will be displayed, when selecting
થી
in the Event output EV2 allocation
in the Event output EV2 allocation setting. in the Event output EV2 allocation setting. in the Event output EV2 allocation setting.
– 86 –
અક્ષરો, ફેક્ટરી ડિફોલ્ટ
સેટિંગ આઇટમ, ફંક્શન, સેટિંગ રેન્જ
Event output EV3 allocation setting · Selects Event output EV3 from Event output allocation table.
· Selection item: Same as the Event output EV1 allocation setting
When (Option 1: EV3) is attached, it will be displayed during EVT3.
EV3 enabled/disabled selection when alarm sets 0 · When alarm value is 0 (zero), alarm action can be Enabled or Disabled.
· પસંદગીની વસ્તુ:
અક્ષમ
સક્ષમ
This setting item will be displayed, when selecting alarm actions
થી
in the Event output
EV3 allocation setting.
EV3 hysteresis setting
· Sets EV3 alarm hysteresis.
સેટિંગ રેન્જ: 0.1 થી 1000.0 (0.1 થી 1800.0)
ડીસી વોલ્યુમtage, current inputs: 1 to 10000
This setting item will be displayed, when selecting
થી
in the Event output EV3 allocation
સેટિંગ
EV3 action delay timer setting
· Sets EV3 alarm action delay time.
સેટિંગ રેન્જ: 0 થી 10000
This setting item will be displayed, when selecting
થી
in the Event output EV3 allocation
સેટિંગ
EV3 action Energized/De-energized setting
· Selects Energized/De-energized status for EV3 alarm.
· પસંદગીની વસ્તુ:
ઉત્સાહિત
ડી-એનર્જાઇઝ્ડ
This setting item will be displayed, when selecting
થી
in the Event output EV3 allocation
સેટિંગ
EV3 output latch selection
· Selects hold when EV3 output is ON.
· પસંદગીની વસ્તુ:
અક્ષમ
સક્ષમ
This setting item will be displayed, when selecting
થી
in the Event output EV2 allocation
સેટિંગ
TS3 output step number
· Sets TS3 output step number.
સેટિંગ રેન્જ: 1 થી 16
This setting item will be displayed, when selecting
TS3 OFF time setting · Sets TS3 OFF time setting.
in the Event output EV3 allocation setting.
સેટિંગ રેન્જ: 00:00 થી 99:59
This setting item will be displayed, when selecting
in the Event output EV3 allocation setting.
TS3 ON time setting · Sets TS3 ON time setting.
સેટિંગ રેન્જ: 00:00 થી 99:59
This setting item will be displayed, when selecting
in the Event output EV3 allocation setting.
– 87 –
[Energized/De-energized]જ્યારે
(Energized) is selected, each Event output is conductive (ON) while each indicator is lit.
Each event output is not conductive (OFF) while each indicator is not lit.
જ્યારે
(De-energized) is selected, each Event output 1 or 2 is not conductive (OFF) while each
સૂચક પ્રગટાવવામાં આવે છે.
Each event output is conductive (ON) while each indicator is not lit.
Event output indicator Event output
ઉત્સાહિત
ON
ડી-એનર્જાઇઝ્ડ
બંધ
When allocated to multiple EVT outputs, the set value is common. Loop error alarms are evaluated at each loop break alarm time setting; if a normal condition is detected
after an error is detected, the error is cleared.
Loop break alarm time setting:
0 થી 200 મિનિટ
Loop break alarm band setting:
0 to 150 (0 to 270 ) or 0.0 to 150.0 (0.0 to 270.0 )
ડીસી વોલ્યુમtage, current inputs: 0 to 1500
Loop break alarm dead band setting:
0 to 150 (0 to 270 ) or 0.0 to 150.0 (0.0 to 270.0 )
ડીસી વોલ્યુમtage, current inputs: 0 to 1500
Alert determination area
Alarm determination stop area
Alert determination area
SV
Loop break alarm dead band setting
(ફિગ. 7.9-1- XNUMX-XNUMX)
Output: Event outputs allocated to alarm outputs in event output setting mode
પસંદગી આઇટમ
પસંદગી
Event output EV allocation setting
: Loop break alarm output
[Time Signal Output]When selecting the time signal output in the event output allocation selection, during program
operation, when the TS output execution step is reached, the event output turns ON for a duration
where TS OFF time elapsed time (TS OFF time + TS ON time).
પસંદગી આઇટમ
પસંદગી
Event output EV allocation setting
: Timing signal output
– 88 –
[Pattern end output] When pattern end output is selected in the event output allocation setting, the pattern end output isgenerated after program completion, and the SV Display flashes [ ]. The output turns off with the
STOP operation.
Selection item Event output EV allocation setting
Selection : Pattern end output
[Remote output] When remote output is selected in the event output allocation setting, it becomes possible to forciblyturn output ON/OFF from the host.
Selection item Event output EV allocation setting
Selection : R
દસ્તાવેજો / સંસાધનો
![]() |
Shinko ACS2 Digital Indicating Controller [પીડીએફ] સૂચના માર્ગદર્શિકા ACS2 Digital Indicating Controller, ACS2, Digital Indicating Controller, Indicating Controller, Controller |